EMR-5000
IM02602012E
Parameter
Description
Setting range
Default
Menu path
Interl OPEN1
Interlocking of the OPEN command
1..n, Assignment
List
-.-
[Control
/Bkr
/Interlockings]
Interl OPEN2
Interlocking of the OPEN command
1..n, Assignment
List
-.-
[Control
/Bkr
/Interlockings]
Interl OPEN3
Interlocking of the OPEN command
1..n, Assignment
List
-.-
[Control
/Bkr
/Interlockings]
SC CLOSE
Switching CLOSE Command, e.g. the state of the Logics
or the state of the digital input
1..n, DI-LogicList
-.-
[Control
/Bkr
/Ex OPEN/CLOSE
Cmd]
SC OPEN
Switching OPEN Command, e.g. the state of the Logics
or the state of the digital input
1..n, DI-LogicList
-.-
[Control
/Bkr
/Ex OPEN/CLOSE
Cmd]
t-TripCmd
Minimum hold time of the OPEN-command (Breaker,
load break switch)
0 - 300.00s
0.2s
[Control
/Bkr
/Trip Manager]
Latched
Defines whether the Relay Output will be Latched when it
picks up.
Inactive,
Active
Inactive
[Control
/Bkr
/Trip Manager]
Ack TripCmd
Ack TripCmd
1..n, Assignment
List
-.-
[Control
/Bkr
/Trip Manager]
Trigger1
Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds
50P[1].TripCmd
[Control
/Bkr
/Trip Manager]
Trigger2
Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds
50P[2].TripCmd
[Control
/Bkr
/Trip Manager]
www.eaton.com
433