EMR-5000
IM02602012E
Motor Start Module Input States
Name
Description
Assignment via
RemStartBlock-I
State of the module input: Remote Motor Start Blocking
[Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
EmgOvr-I
State of the module input: Emergency Override. Signal has to be
active in order to release the thermal capacity of the motor. Please
notice that by doing this you run the risk of damaging the motor.
“EMGOVR” has to be set to “DI” or “DI or UI” for this input to take
effect
[Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
INSQ-I
State of the module input: INcomplete SeQuence
[Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
ZSS-I
State of the module input: Zero Speed Switch
[Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
STPC Blo-I
State of the module input: With this setting a Digital Input keeps the
Motor in the RUN mode, even when the motor current drops below
STPC (motor stop current).
[Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
www.eaton.com
497