EMR-5000
IM02602012E
Device Planning Parameters of the Motor Wellnes
Parameter
Description
Options
Default
Menu path
Mode
Mode
Do not use,
Use
Use
[Device Planning]
Global Protection Parameters of the Motor Wellnes
Parameter
Description
Setting range
Default
Menu path
ExBlo1
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Motor Diagnosis
/BRB Detection]
ExBlo2
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Motor Diagnosis
/BRB Detection]
HP
Horse Power
1 - 500000
500
[Protection Para
/Global Prot Para
/Motor Diagnosis
/BRB Detection]
Num Pole Pairs
Number of pole pairs of the motor
1 - 16
4
[Protection Para
/Global Prot Para
/Motor Diagnosis
/BRB Detection]
Num Rotor Bars
Number of Rotor Bars
10 - 5000
55
[Protection Para
/Global Prot Para
/Motor Diagnosis
/BRB Detection]
Rotor Diameter
Diameter of the Rotor
0.1 - 10
0.6
[Protection Para
/Global Prot Para
/Motor Diagnosis
/BRB Detection]