Apply a balanced three-phase current system (nominal currents).
Switch off IA (the threshold value »
Threshold« for
»
I2 Fund.« must be below 33%).
Measure the tripping time.
The present current unbalance
»
I2 Fund.« corresponds with 1/3 of the existing phase current displayed.