EMR-5000
IM02602012E
Setting Group Parameters of the Frequency Protection Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Freq-Prot
/81[1]]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Freq-Prot
/81[1]]
Blo TripCmd
Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
81[1]: Inactive
81[2]: Active
81[3]: Inactive
81[4]: Active
81[5]: Inactive
81[6]: Active
[Protection Para
/<1..4>
/Freq-Prot
/81[1]]
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Freq-Prot
/81[1]]
81O-Over
Pickup value for overfrequency.
Only available if: Device Planning: 81.Mode = 81O-Over
Or 81OR- Over & df/dt Or 81ODR- Over & DF/DT
40.00 - 69.95Hz
81[1]: 61.00Hz
81[2]: 61.0Hz
81[3]: 51.00Hz
81[4]: 51.00Hz
81[5]: 51.00Hz
81[6]: 51.00Hz
[Protection Para
/<1..4>
/Freq-Prot
/81[1]]
81U-Under
Pickup value for underfrequency.
Only available if: Device Planning: 81.Mode = 81U-Under
Or 81UR- Under & df/dt Or 81UDR- Under & DF/DT
40.00 - 69.95Hz
81[1]: 59.0Hz
81[2]: 49.00Hz
81[3]: 59.0Hz
81[4]: 59.0Hz
81[5]: 59.0Hz
81[6]: 59.0Hz
[Protection Para
/<1..4>
/Freq-Prot
/81[1]]