EMR-5000
IM02602012E
Parameter
Description
Setting range
Default
Menu path
Pickup P<
Under(load) Active Power Pickup Value (e.g.: caused by
idling motors). Definition for VAn is as follows: VAn =
SQRT(3) * VT secondary rating * CT secondary rating
(I=1/5A) for wye or VAn = 3 * VT secondary
rating/SQRT(3) * CT secondary rating (I=1/5A) for delta
connections.
Only available if: Device Planning: PQS.Mode = Pickup
P<
0.003 - 10.000VAn
0.80VAn
[Protection Para
/<1..4>
/Power-Prot
/32[1]]
Pickup Pr>
Overload Reverse Active Power Pickup Value. Protection
against reverse feeding into the power supply network.
Definition for VAn is as follows: VAn = SQRT(3) * VT
secondary rating * CT secondary rating (I=1/5A) for wye
or VAn = 3 * VT secondary rating/SQRT(3) * CT
secondary rating (I=1/5A) for delta connections.
Only available if: Device Planning: PQS.Mode = Pickup
Pr>
0.003 - 10.000VAn
0.020VAn
[Protection Para
/<1..4>
/Power-Prot
/32[1]]
Pickup Pr<
Under Reverse Definition for VAn is as follows: VAn =
SQRT(3) * VT secondary rating * CT secondary rating
(I=1/5A) for wye or VAn = 3 * VT secondary
rating/SQRT(3) * CT secondary rating (I=1/5A) for delta
connections.
Only available if: Device Planning: PQS.Mode = Pickup
Pr<
0.003 - 10.000VAn
0.80VAn
[Protection Para
/<1..4>
/Power-Prot
/32[1]]
t
Tripping delay
0.00 - 1100.00s
0.01s
[Protection Para
/<1..4>
/Power-Prot
/32[1]]
States of the Inputs of the Power Protection Module
Name
Description
Assignment via
ExBlo1-I
Module Input State: External Blocking
[Protection Para
/Global Prot Para
/Power-Prot
/32[1]]
ExBlo2-I
Module Input State: External Blocking
[Protection Para
/Global Prot Para
/Power-Prot
/32[1]]