EMR-5000
IM02602012E
Set Parameters of the Power Factor Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
Blo TripCmd
Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
PF-55D[1]:
Inactive
PF-55D[2]: Active
PF-55A[1]:
Inactive
PF-55A[2]: Active
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
Trig Mode
Trigger Mode. Should the Module be triggered if the
Current Phasor is leading to the Voltage Phasor = Lead?
Or should the Module be triggered if the Current Phasor
is lagging to the Voltage Phasor = Lag?
leading,
lagging
lagging
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
Trigger-PF
This is the power factor where the relay will pick up
0.5 - 0.99
0.7
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
Res Mode
Trigger Mode. Should the Module be triggered if the
Current Phasor is leading to the Voltage Phasor = Lead?
Or should the Module be triggered if the Current Phasor
is lagging to the Voltage Phasor = Lag?
leading,
lagging
lagging
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
www.eaton.com
738