EMR-5000
IM02602012E
Parameter
Description
Setting range
Default
Menu path
Reset-PF
This setting is the power factor, at which the relay will
reset the power factor trip. It is like setting a hysteresis
for the Trigger setting.
0.5 - 0.99
0.9
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
t-trip
Tripping delay
0.00 - 300.00s
0.00s
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
t-Pickup Comp
Pre-trigger time for the Compensation Signal. When this
timer is elapsed the compensation signal will be
activated.
0.00 - 300.00s
5.00s
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
t-Reset Comp
Reset (Post-trigger) time of the Compensation Signal.
When this timer is elapsed the compensation signal will
be deactivated.
0.00 - 300.00s
5.00s
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
States of the Inputs of the Power Factor Module
Name
Description
Assignment via
ExBlo1-I
Module Input State: External Blocking
[Protection Para
/Global Prot Para
/Power Factor-Prot
/PF-55D[1]]
ExBlo2-I
Module Input State: External Blocking
[Protection Para
/Global Prot Para
/Power Factor-Prot
/PF-55D[1]]
ExBlo TripCmd-I
Module Input State: External Blocking of the Trip Command
[Protection Para
/Global Prot Para
/Power Factor-Prot
/PF-55D[1]]