EMR-5000
IM02602012E
Parameter
Description
Setting range
Default
Menu path
LB 1 Trip
Load Bearing 1 Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB 1]
LB 2 Alarm Function Load Bearing 2 Alarm Function
Inactive,
Active
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB 2]
LB 2 Trip Function
Load Bearing 2 Trip Function
Inactive,
Active
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB 2]
LB 2 Alarm
Load Bearing 2 Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB 2]
LB 2 t-Delay
Load Bearing 2 If this time is expired a Temperature
Alarm will be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min
1min
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB 2]
LB 2 Trip
Load Bearing 2 Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB 2]
Aux1 Alarm
Function
Auxiliary 1 Alarm Function
Inactive,
Active
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux1]
www.eaton.com
769