EMR-5000
IM02602012E
Parameter
Description
Setting range
Default
Menu path
MB Alarm Function Motor Bearing Alarm Function
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB Group]
MB Trip Function
Motor Bearing Trip Function
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB Group]
MB Alarm
Motor Bearing Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB Group]
MB t-Delay
Motor Bearing If this time is expired a Temperature Alarm
will be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min
1min
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB Group]
MB Trip
Motor Bearing Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C
100°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB Group]
LB Alarm Function
Load Bearing Alarm Function
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB Group]
LB Trip Function
Load Bearing Trip Function
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB Group]
www.eaton.com