EMR-5000
IM02602012E
Signal
Description
MB 1 Trip
Motor Bearing 1 Signal: Trip
MB 1 Alarm
Motor Bearing 1 Alarm RTD Temperature Protection
MB 1 Timeout Alarm
Motor Bearing 1 Timeout Alarm
MB 1 Invalid
Motor Bearing 1 Signal: Invalid Temperature Measurement Value (e.g caused by an defective or
interrupted RTD Measurement)
MB 2 Trip
Motor Bearing 2 Signal: Trip
MB 2 Alarm
Motor Bearing 2 Alarm RTD Temperature Protection
MB 2 Timeout Alarm
Motor Bearing 2 Timeout Alarm
MB 2 Invalid
Motor Bearing 2 Signal: Invalid Temperature Measurement Value (e.g caused by an defective or
interrupted RTD Measurement)
LB 1 Trip
Load Bearing 1 Signal: Trip
LB 1 Alarm
Load Bearing 1 Alarm RTD Temperature Protection
LB 1 Timeout Alarm
Load Bearing 1 Timeout Alarm
LB 1 Invalid
Load Bearing 1 Signal: Invalid Temperature Measurement Value (e.g caused by an defective or
interrupted RTD Measurement)
LB 2 Trip
Load Bearing 2 Signal: Trip
LB 2 Alarm
Load Bearing 2 Alarm RTD Temperature Protection
LB 2 Timeout Alarm
Load Bearing 2 Timeout Alarm
LB 2 Invalid
Load Bearing 2 Signal: Invalid Temperature Measurement Value (e.g caused by an defective or
interrupted RTD Measurement)
Aux1 Trip
Auxiliary 1 Signal: Trip
Aux1 Alarm
Auxiliary 1 Alarm RTD Temperature Protection
Aux1 Timeout Alarm
Auxiliary 1 Timeout Alarm
Aux1 Invalid
Auxiliary 1 Signal: Invalid Temperature Measurement Value (e.g caused by an defective or
interrupted RTD Measurement)
Aux2 Trip
Auxiliary 2 Signal: Trip
Aux2 Alarm
Auxiliary 2 Alarm RTD Temperature Protection
Aux2 Timeout Alarm
Auxiliary 2 Timeout Alarm
Aux2 Invalid
Auxiliary 2 Signal: Invalid Temperature Measurement Value (e.g caused by an defective or
interrupted RTD Measurement)
Trip WD Group
Trip all Windings
Alarm WD Group
Alarm all Windings
TimeoutAlmWDGrp
Timeout Alarm all Windings
WD Group Invalid
Winding Group Signal: Invalid Temperature Measurement Value (e.g caused by an defective or
interrupted RTD Measurement)
Trip MB Group
Trip all Motor Bearings
Alarm MB Group
Alarm all Motor Bearings
TimeoutAlmMBGrp
Timeout Alarm all Motor Bearings
MB Group Invalid
Motor Bearing Group Signal: Invalid Temperature Measurement Value (e.g caused by an
defective or interrupted RTD Measurement)
www.eaton.com
781