EMR-5000
IM02602012E
RTD Temperature Protection Module Counter Values
Value
Description
Default
Size
Menu path
Hottest WD
Hottest motor winding temperature in degrees C. 0°C
0 - 200°C
[Operation
/Measured Values
/URTD]
Hottest MB
Hottest motor bearing temperature in degrees C.
Resettable with "Sys Res OperationsCr" or "All".
0°C
0 - 200°C
[Operation
/Measured Values
/URTD]
Hottest LB
Hottest load bearing temperature in degrees C.
Resettable with "Sys Res OperationsCr" or "All".
0°C
0 - 200°C
[Operation
/Measured Values
/URTD]
Hottest Aux
Hottest Auxiliary temperature in degrees C.
Resettable with "Sys Res OperationsCr" or "All".
0°C
0 - 200°C
[Operation
/Measured Values
/URTD]
HighestWdTemp
Highest motor winding temperature in degrees.
Resettable with "Sys Res OperationsCr" or "All".
0°C
0 - 250°C
[Operation
/History
/OperationsCr]
HighestMbTemp
Highest motor bearing temperature in degrees.
Resettable with "Sys Res OperationsCr" or "All".
0°C
0 - 250°C
[Operation
/History
/OperationsCr]
HighestLbTemp
Highest load bearing temperature in degrees.
Resettable with "Sys Res OperationsCr" or "All".
0°C
0 - 250°C
[Operation
/History
/OperationsCr]
HighestAuxTemp
Highest Auxiliary temperature in degrees.
Resettable with "Sys Res OperationsCr" or "All".
0°C
0 - 250°C
[Operation
/History
/OperationsCr]
nWdAlarms
Number of winding temperature alarms since last
reset. Resettable with "Sys Res Alarm" or "All".
0
0 - 65535
[Operation
/History
/PickupCr]
nMbAlarms
Number of motor bearing temperature alarms
since last reset. Resettable with "Sys Res Alarm"
or "All".
0
0 - 65535
[Operation
/History
/PickupCr]
www.eaton.com
783