EMR-5000
IM02602012E
Forcing Analog Inputs*
* = Availability depends on ordered device.
The parameters, their defaults, and setting ranges have to be taken from
Analog Inputs section.
Principle – General Use
The User MUST ENSURE that the Analog Inputs operate normally after
maintenance is completed.
For commissioning purposes or for maintenance, Analog Inputs can be set by force.
Within this mode [Service/Test Mode (Prot inhibit)/WARNING! Cont?/Analog Inputs], Analog Inputs can be set by force:
Permanent; or
Via timeout.
If they are set with a timeout, they will keep their “Forced Value” only as long as this timer runs.
If the timer
expires, the
Analog Input will operate normally.
If they are set as »
Permanent«, they will keep the “Forced Value” continuously.
This menu will show the current value that is fed to the Analog Input until the User activates the force mode by calling
up the »
Function«. As soon as the force mode is activated, the shown value will be frozen as long as this mode is
active. Now the User can force the Analog Input value. As soon as the force mode is deactivated, measured value will
be shown again.
www.eaton.com
897