EMR-5000
IM02602012E
Parameter
Description
Setting range
Default
Menu path
Ex Start Simulation
External Start of Fault Simulation (Using the test
parameters)
1..n, Assignment
List
-.-
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Process]
ExBlo
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
Bkr.Pos CLOSE
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Process]
Ex ForcePost
Force Post state. Abort simulation.
1..n, Assignment
List
-.-
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Process]
Voltage Parameter of the Failure Simulator
Parameter
Description
Setting range
Default
Menu path
VA Fund.
Voltage Fundamental Magnitude in Pre State: Phase A
0.00 - 1.30Vn
0.57Vn
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PreFault
/VT]
VB Fund.
Voltage Fundamental Magnitude in Pre State: Phase B
0.00 - 1.30Vn
0.57Vn
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PreFault
/VT]
www.eaton.com
902