EMR-5000
IM02602012E
Parameter
Description
Setting range
Default
Menu path
VC Fund.
Voltage Fundamental Magnitude during Post phase:
Phase C
0.00 - 1.30Vn
0.57Vn
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PostFault
/VT]
VX Fund.
Voltage Fundamental Magnitude during Post phase:
Phase VX
0.00 - 1.30Vn
0.0Vn
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PostFault
/VT]
Angle VA Fund.
Start Position respectively Start Angle of the Voltage
Phasor during Post phase: Phase A
-360 - 360°
0°
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PostFault
/VT]
Angle VB Fund.
Start Position respectively Start Angle of the Voltage
Phasor during Post phase: Phase B
-360 - 360°
240°
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PostFault
/VT]
www.eaton.com
907