Zone Interlocking
Only for Zone Interlock Tripping Outputs (Zone Interlock, semiconductor
output): 5 Vdc, <2mA for connection to electronic inputs only.
Zone Out:
Output voltage (High)
4.75 to 5.25 Vdc
Output voltage (Low)
0.0 to +0.5 Vdc
Zone In:
Nominal input voltage
+5 Vdc
Max. input voltage
+5.5 Vdc
Switching threshold ON
min. 4.0 Vdc
Switching threshold OFF
max. 1.5 Vdc
Galvanic isolation
2.5 kV ac (to ground and other IO)
Connection:
Screw-type terminals (twisted pair)
www.eaton.com