EMR-5000
IM02602012E
Analog Outputs
Available Elements:
AnOut[1] ,AnOut[2]
The E-Series relays can be programmed to output for three different ranges of either 0- 20mA, 4- 20 mA, or 0-10 Volts.
These outputs can be configured by the User to represent the status of User programmed parameters that are available
from the relay. The User will find the configuration menu for this feature under the [Device Para/ Analog Outputs] menu
option. Here the User can define to which parameter the output will correlate. As with any parameter, a password is
required to configure this feature.
To program this feature, the User will select the Analog Outputs option under the main menu item “Device PARA”.
Then select the wrench icon which will allow the assignment of the output to a parameter monitored by the relay.
The available signals,
that
can be assigned onto the analog outputs are shown in the “List of Analog Outputs”.
Once the assignment has been made, the User can select the expected range of the parameter that will correlate to the
analog output. The User will be required to enter a “Range min”, and “Range max”. The “Range min” will determine the
value at which e.g. 4 mA will be transmitted by the relay. Likewise, the “Range max” value will determine the value that
will result in the transmission of a 20 mA output. The same applies when the output is configured to 0- 10 Volts.