EMR-5000
IM02602012E
Program Mode
By means of the
Program Mode, parameter settings can be locked against any changes as long as one or all of the
breaker(s) are in the »
CLOSED« position. The Program Mode can be activated within the [System Para/General
Settings/Program Mode Bypass] menu.
»Both Bkr Open« - Parameter changes require all breakers to be in the »OPEN« state.
»Either Bkr Open or Close« - Parameter changes do not require the breaker to be in the »OPEN« state.
Unlike, if the
Program Mode is used for Motor Protection devices, the user has the following options:
»Motor Stop« - Lock parameter changes, if the motor is not in the »STOP« state.
This ensures, that parameter changes can only be done while the motor stands still (zero speed).
»Either Motor Stopped or Running« - Parameter changes do not require the motor to be in the »Motor stop« state.
Bypass of the Program Mode
The program mode can be bypassed by means of the Direct Control Parameter »
Program Mode Bypass«. The
protective device will fall back into the program mode either:
Directly after a parameter change has been saved, else
10 minutes after the bypass has been activated.