46 - Current Unbalance Protection
Elements:
46[1] ,46[2]
This is the
46
device Current Unbalance setting, which works similar to the
47
device Voltage Unbalance setting. The
positive and negative sequence currents are calculated from the 3-phase currents. The Threshold setting defines a
minimum operating current magnitude of either I1 or I2 for the 46 function to operate, which insures that the relay has a
solid basis for initiating a current unbalance trip. The »
%(I2/I1)«
setting is the unbalance trip pickup setting. It is
defined by the ratio of negative sequence current to positive sequence current »
%(I2/I1)«
for ABC rotation and »
%
(I1/I2)«
for ACB rotation. The device will automatically select the correct ratio based on the Phase Sequence setting in
the System Configuration group described above.
This function requires positive or negative sequence current magnitude above the threshold setting and the percentage
current unbalance above the »
%(I2/I1)« setting before allowing a current unbalance trip. Therefore, both the threshold
and percent settings must be met for the specified Delay time setting before the relay initiates a trip for current
unbalance.
All elements are identically structured.