EMR-5000
IM02602012E
DI-8P X
Name of the Assembly group:
DI-8P X1
Device Parameters of the Digital Inputs on DI-8P X
Parameter
Description
Setting range
Default
Menu path
Nom Voltage
Nominal voltage of the digital inputs
24 V dc,
48 V dc,
60 V dc,
110/120 V dc,
230/240 V dc,
110/120 V ac,
230/240 V ac
110/120 V dc
[Device Para
/Digital Inputs
/DI-8P X1
/Group 1]
Inverting 1
Inverting the input signals.
Inactive,
Active
Inactive
[Device Para
/Digital Inputs
/DI-8P X1
/Group 1]
Debouncing Time 1 A change of the state of a digital input will only be
recognized after the debouncing time has expired
(become effective). Thus, transient signals will not be
misinterpreted.
No Debouncing
Time,
20 ms,
50 ms,
100 ms
20 ms
[Device Para
/Digital Inputs
/DI-8P X1
/Group 1]
Nom Voltage
Nominal voltage of the digital inputs
24 V dc,
48 V dc,
60 V dc,
110/120 V dc,
230/240 V dc,
110/120 V ac,
230/240 V ac
110/120 V dc
[Device Para
/Digital Inputs
/DI-8P X1
/Group 2]
Inverting 2
Inverting the input signals.
Inactive,
Active
Inactive
[Device Para
/Digital Inputs
/DI-8P X1
/Group 2]
www.eaton.com
76