Instruction  Leaflet  

IL29C204I

Effective October 2011

Installation Instructions for Motor Operator for

 

3- and 4-Pole ND, NB, NC, MD, MA, MC Type

 

Circuit Breakers and Molded Case Switches

EATON CORPORATION

 www.eaton.com

WARNING 

CONTACT WITH ENERGIZED EQUIPMENT CAN 

RESULT IN DEATH, SEVERE PERSONAL INJURY, OR 

SUBSTANTIAL PROPERTY DAMAGE. DO NOT 

NANCE ON EQUIPMENT WHILE IT IS ENERGIZED. 

ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT 

BEFORE PROCEEDING WITH THE TASK, AND 

ALWAYS FOLLOW GENERALLY ACCEPTED SAFETY 

PROCEDURES. 

ATTEMPT TO INSTALL OR PERFORM MAINTE- 

EATON IS NOT LIABLE FOR THE MISAPPLICATION

OR MISINSTALLATION OF ITS PRODUCTS.

The user is cautioned to observe all recommendations, 

warnings, and cautions relating to the safety of personnel 

and equipment as well as all general and local health and 

safety laws, codes, and procedures. 

The recommendations and information contained herein 

are based on Eaton experience and judgement, but should 

not be considered to be all-inclusive or covering every 

application or circumstance which may arise. If any ques- 

instructions. 

1. 

INTRODUCTION 

The motor operator (Fig. 1-1) allows the circuit breaker to 

be opened, closed, or reset remotely. It has the capability 

for lock-off, push-to-trip, and manual operation. Electrical 

The motor operator mechanism is driven by a reversible 

electric motor connected to a ball screw. The ball screw 

drives the circuit breaker handle. Limit switches are used 

to control the motor. 

installed to gain access to the breaker’s cable terminals, 

Fig. 2-3. 

Fig. 1-1.  Motor Operator Installed in ND Type Frame 

Series C Circuit Breaker 

2. 

INSTALLATION 

The motor operator is Underwriters Laboratories, Inc. 

listed as a recognized component suitable for field instal- 

lation on N-frame circuit breakers and molded case 

switches under UL File E64124.

The motor operator is normally supplied as a separate 

item for mounting on an uninstalled circuit breaker. If a 

motor operator is to be mounted on an installed circuit 

breaker, all power must be removed from the circuit 

 

If the motor operator is to be installed on an OPTIM

breaker, an OPTIM Connector Kit, Catalog Number

be connected on the face of the operator.  The kit

the trip unit port.

tions arise, contact Eaton for further information or 

power to the motor is cut off when the cover is removed. 

It is unnecessary  to remove a motor operator once 

OPEOPCK, should be ordered to allow the Optimizer to 

includes a connector socket and an extension cable to

breaker before proceeding  to mount the motor operator. 

Summary of Contents for EOP5T07

Page 1: ...1 Instruction Leaflet IL29C204I Installation Instructions for Motor Operator for 3 and 4 Pole ND NB NC MD MA MC Type Circuit Breakers and Molded Case Switches Contents Description Page 1 Introduction...

Page 2: ...ed or reset remotely It has the capability for lock off push to trip and manual operation Electrical The motor operator mechanism is driven by a reversible electric motor connectedto a ball screw The...

Page 3: ...r operator is mounted to the cir cuit breaker the circuit breaker nameplate is not visi ble Before mounting the motor operator make sure the circuit breaker nameplateinformation is recorded for future...

Page 4: ...nd the push nut insidethe operator Use two 4 in pan head screws The handle extension must be between the rollers of the bracket assem bly and the motor towards the line end of the breaker Figs 2 3 4 1...

Page 5: ...cking arm white line to the Manual Operation mode In this mode electrical power to the motor is cut off Figs 3 1 and 3 3 CAUTION IF BREAKERISTRIPPED WHEN OFF MOTOR OPER ATOR MUST BE RECYCLEDTO ON THEN...

Page 6: ...otor Operator for 3 and 4 Pole ND NB NC MD MA MCType Circuit Breakers and Molded Case Switches EATON CORPORATION www eaton com Fig 3 1 Motor Operator Features Fig 3 2 Motor Operator in Electrical Posi...

Page 7: ...sert into the 30 in dia hole near the POWER OFF switch to hold switch ON Figs 3 1 and 4 1 CAUTION 125 IN DIA PIN SHOULD BE REMOVED BEFORE REINSTALLING THE COVER 4 4 For upper limit switch adjustment l...

Page 8: ...Operator is an intermittent duty device The safe duty cycle OFF to ON to OFF should not exceed one per minute Electrical Operating times at rated voltage a To turn breaker ON 0 2 second 12 cycles max...

Page 9: ...uction Leaflet IL29C204I Effective Octoberr 2011 Installation Instructions for Motor Operator for 3 and 4 Pole ND NB NC MD MA MCType Circuit Breakers and Molded Case Switches EATON CORPORATION www eat...

Page 10: ...tion Leaflet IL29C204I Effective October 2011 Installation Instructions for Motor Operator for 3 and 4 Pole ND NB NC MD MA MCType Circuit Breakers and Molded Case Switches EATON CORPORATION www eaton...

Page 11: ...tion Leaflet IL29C204I Effective Octoberr 2011 Installation Instructions for Motor Operator for 3 and 4 Pole ND NB NC MD MA MCType Circuit Breakers and Molded Case Switches EATON CORPORATION www eaton...

Page 12: ...zed Eaton sales represent a tive The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement b...

Reviews: