Instruction  Leaflet  

IL29C204I

Effective October 2011

Installation Instructions for Motor Operator for

 

3- and 4-Pole ND, NB, NC, MD, MA, MC Type

 

Circuit Breakers and Molded Case Switches

EATON CORPORATION

 www.eaton.com

WARNING

 

BEFORE MOUNTING A MOTOR OPERATOR ON A 

CIRCUIT BREAKER INSTALLED IN AN ELECTRICAL 

SYSTEM, MAKE SURE THE CIRCUIT BREAKER 

IS 

SWITCHED TO THE 

OFF POSITION AND THAT 

THERE 

IS NO VOLTAGE PRESENT WHERE WORK IS 

TO BE PERFORMED. SPECIAL ATTENTION SHOULD 

BE PAID TO REVERSE FEED APPLICATIONS TO 

ENSURE NO VOLTAGE 

IS PRESENT. THE VOLTAGES 

IN ENERGIZED EQUIPMENT CAN CAUSE DEATH 

OR 

SEVERE PERSONAL INJURY. 

CAUTION 

ENERGIZING THE MOTOR OPERATOR WHEN IT 

IS 

AGE IT. ENSURE THAT THE MOTOR OPERATOR 

IS 

SECURELY MOUNTED TO A CIRCUIT BREAKER 

BEFORE OPERATING ELECTRICALLY. 

NOT MOUNTED TO A CIRCUIT BREAKER MAY DAM

Note: When the motor operator is mounted to the cir- 

cuit breaker, the circuit breaker nameplate is not visi- 

ble. Before mounting the motor operator, make sure 

the circuit breaker nameplate information is recorded 

for future reference. 

A blank nameplate is supplied 

for this purpose. The nameplate should be placed on 

the top side of the motor operator. 

To install the electrical operator perform the following 

steps: 

2-1. 

2-2. 

2-3. 

2-4. 

Remove motor operator from packing. Inspect it for 

completeness (Fig. 2-1). Check the motor operator 

nameplate to make sure that the rating agrees with 

the installation requirements; and make sure that 

mounting hardware is included. 

Install circuit breaker handle extension using nuts 

and screws supplied. (See Fig. 2-3.) 

Assemble top mounting plate (spacer) with 3.75-in. 

flat head screws supplied (Figs. 2-1, 2-3, 4-2). 

Motor operator frame is to mount to this top plate 

motor operator to the circuit breaker with screws 

Fig. 2-1  Motor Operator Kit 

using two .500-in. pan head screws. 

Trip breaker to the 

"TRIP" 

 

 

e

h

t

n

u

o

M

 .

n

o

it

i

s

o

p

Summary of Contents for EOP5T07

Page 1: ...1 Instruction Leaflet IL29C204I Installation Instructions for Motor Operator for 3 and 4 Pole ND NB NC MD MA MC Type Circuit Breakers and Molded Case Switches Contents Description Page 1 Introduction...

Page 2: ...ed or reset remotely It has the capability for lock off push to trip and manual operation Electrical The motor operator mechanism is driven by a reversible electric motor connectedto a ball screw The...

Page 3: ...r operator is mounted to the cir cuit breaker the circuit breaker nameplate is not visi ble Before mounting the motor operator make sure the circuit breaker nameplateinformation is recorded for future...

Page 4: ...nd the push nut insidethe operator Use two 4 in pan head screws The handle extension must be between the rollers of the bracket assem bly and the motor towards the line end of the breaker Figs 2 3 4 1...

Page 5: ...cking arm white line to the Manual Operation mode In this mode electrical power to the motor is cut off Figs 3 1 and 3 3 CAUTION IF BREAKERISTRIPPED WHEN OFF MOTOR OPER ATOR MUST BE RECYCLEDTO ON THEN...

Page 6: ...otor Operator for 3 and 4 Pole ND NB NC MD MA MCType Circuit Breakers and Molded Case Switches EATON CORPORATION www eaton com Fig 3 1 Motor Operator Features Fig 3 2 Motor Operator in Electrical Posi...

Page 7: ...sert into the 30 in dia hole near the POWER OFF switch to hold switch ON Figs 3 1 and 4 1 CAUTION 125 IN DIA PIN SHOULD BE REMOVED BEFORE REINSTALLING THE COVER 4 4 For upper limit switch adjustment l...

Page 8: ...Operator is an intermittent duty device The safe duty cycle OFF to ON to OFF should not exceed one per minute Electrical Operating times at rated voltage a To turn breaker ON 0 2 second 12 cycles max...

Page 9: ...uction Leaflet IL29C204I Effective Octoberr 2011 Installation Instructions for Motor Operator for 3 and 4 Pole ND NB NC MD MA MCType Circuit Breakers and Molded Case Switches EATON CORPORATION www eat...

Page 10: ...tion Leaflet IL29C204I Effective October 2011 Installation Instructions for Motor Operator for 3 and 4 Pole ND NB NC MD MA MCType Circuit Breakers and Molded Case Switches EATON CORPORATION www eaton...

Page 11: ...tion Leaflet IL29C204I Effective Octoberr 2011 Installation Instructions for Motor Operator for 3 and 4 Pole ND NB NC MD MA MCType Circuit Breakers and Molded Case Switches EATON CORPORATION www eaton...

Page 12: ...zed Eaton sales represent a tive The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement b...

Reviews: