Eaton ePDU G3 Troubleshooting Guide P-164000278—Rev 1
www.eaton.com/ePDU
10
Chapter 3
Troubleshooting
This chapter provides details for troubleshooting power outlets for the Eaton Enclosure Power Distribution Unit
(ePDU) G3 models. The following tables list fault conditions, potential causes, and possible troubleshooting
actions you can take in response to problems.
!
IMPORTANT
Be aware that unplugging the ePDU from the power source will turn off power to all connected
loads and equipment.
Power Outlets
Table 5. Power Outlet Troubleshooting
Problem
Possible Root Cause
Actions
Outlet LED is Off: No power to
the outlet, but the Web
interface reports that the
outlet is On
l
Web interface is locked
l
Communication issue
l
Internal issue
l
Wrong IP address: You are
monitoring the wrong ePDU
1 - Press the F5 or page refresh button in the Web browser.
2 - Close and restart the Web browser or try another Web browser,
such as Google Chrome, Firefox, or Opera.
3 - Refer to the
Eaton ePDU G3 Operations Manual
and/or restart the
ePDU Network Management and Control module with the reset button
(R) on the product (press for 1
or 2
seconds). Outlets will not restart
during this process.
4 - Cycle the outlet control (On/Off) using the Web interface. If the
outlet LED is still Off, restart the ePDU and then reconnect the device to
the ePDU.
5 - Check the Media Access Control (MAC) address on the device and
check the MAC address in the Web interface.
Outlet LED is On, but there is
no power to outlet
l
Circuit breaker (CB) has
tripped
l
Internal issue (outlet relay is
open)
1 - Check the CB state on the ePDU.
NOTE
For Managed (MA), Switched (SW), and (optionally)
Metered Input (MI) ePDUs, the LED normally flashes
RED when a CB is tripped. If the LED is alternately
flashing green and red, the outlet is On, but there is a
breaker overload.
2 - Restart the ePDU and check again.
Outlet LED is Off, but there is
power to outlet
l
Internal failure
1 - Cycle the outlet (On/Off) using the Web interface.
2 - Restart the product and check again.
Outlet LED is blinking
l
Critical alarm on the outlet
l
Internal failure
1 - Check the LCD screen. If the LCD screen is flashing red, a critical
alarm is present. Check the outlet settings, measurements, and
electrical conditions. The alarm does not clear until the outlet condition
is back to normal (cannot manually suppress the alarm).
IEC plug falls from the ePDU
during normal operation
l
The cord was not fully seated
before the lever grip switch
was set to close
l
The lever grip switch is set to
open rather than close
1 - Reseat the plug in the outlet, then ensure that the lever grip switch
is pointing to the + sign.
NOTE
If the actions listed in this table do not resolve the problem, contact customer service or a local representative for guidance and/or
replacement (see “Contacting Service and Support” on page 5).