6 Appendix
45
ESR5-BWS-31-24VDC
11/23 MN049020EN Eaton.com
Relay outputs : signal current path 41/42
Source/drain
Interface type
Additional
measure
Source/drain
Suitable interface type
Source
A
M
Drain
A
Source
C0
M
Drain
-
Interface-type A - source
Parameter
min.
normally
max.
Switching current I
i
10 mA
-
6 mA
Switching voltage U
i
5 V
-
250 V AC
Internal resistance R
i
(in switched state)
Load
≥
1 A
≤
100 m
Ω
-
Load
≥
10 mA
≤
20
Ω
Load capacity C
L
-
-
See switching capacity
Inductive load L
L
-
-
See switching capacity
Potential free
Yes
-
-
Additional measure M
The outputs are not types according to IEC 61131-2.
Interface type C0 source
Parameter
min.
normally
max.
Test pulse duration t
i
-
-
-
Test pulse interval T
-
-
-
Rated operational current I
N
-
-
6 A
Load capacity C
L
-
-
See switching capacity
Inductive load L
L
-
-
See switching capacity
Additional measure M
The inputs are not types according to IEC 61131-2.
No test pulses are output at the output.