15 Technical data
22
ESR5-NE-51-24VAC-DC
12/19 MN049002EN
www.eaton.com
General data
Relay type
Electromechanically forcibly guided, dust-proof relay
Nominal operating mode
100 % operating factor
Degree of protection
IP20
Min. degree of protection of inst. location
IP54
Mounting position
any
Mounting type
DIN rail mounting
Air and creepage distances between the power circuits
DIN EN 50178/VDE 0160
Rated insulation voltage
250 V
Rated surge voltage / insulation
Basic insulation 4 kV:
between all current paths and housing
Safe isolation, reinforced insulation 6 kV:
between A1/A2, 11/12, 23/24, 71/72 and 33/34, 43/44,
53/54, 63/64
Pollution degree
2
Surge voltage category
III
Dimensions
W x H x D
22.5 x 99 x 114.5 mm
Connection data
Conductor cross section, solid
0.2 mm
2
- 2.5 mm
2
Conductor cross section, stranded
0.2 mm
2
- 2.5 mm
2
Conductor cross section AWG/kcmil
24
- 12
Stripping length
7 mm
Screw thread
M3
Ambient conditions
Ambient temperature (operation)
-20 °C - 55 °C (Observe derating)
Ambient temperature (storage/transport)
-40 °C - 70 °C
Maximum permissible relative humidity (operation)
75 % (on average, 85 % infrequently, non-condensing)
Maximum permissible humidity (storage/transport)
75 % (on average, 85 % infrequently, non-condensing)
Altitude
max. 2000 m (above sea level)
Shock
15 g
Vibration (operation)
10 Hz -150 Hz, 2 g
Conformance / Approvals
Conformance
CE-compliant
Approvals
Safety data
Stop category according to IEC 60204
0