Safety parameters for IEC 61508 - High demand
SIL
3 (in conjunction with suitable evaluating device)
PFH
d
1.02 x 10
-10
per hour
Demand rate
< 12 months
Proof test interval
240 months
Duration of use
240 months
The specifications apply assuming the following calculation basis:
B
10d
230000 (at 3
A AC-15)
d
op
365.25 days
h
op
24 h
t
Cycle
3600 s
Safety parameters for IEC 61508 - Low demand
SIL
3 (in conjunction with suitable evaluating device)
PFD
avg
1.50 x 10
-4
Proof test interval
84 months
Duration of use
240 months
Safety characteristic data according to EN ISO 13849
Category
4 (in conjunction with suitable evaluating device)
Performance Level
e (in conjunction with suitable evaluating device)
Duration of use
240 months
For applications in PL e, the required demand rate for the safety function is once per month.
The specifications apply assuming the following calculation basis:
B
10d
230000 (at 3
A AC-15)
d
op
365.25 days
h
op
24 h
t
Zyklus
3600 s
Safety parameters for EN 62061
SILCL
3 (in conjunction with suitable evaluating device)