16 Technical data
ESR5-NO-41-24VAC-DC
12/19 MN049009EN
www.eaton.com
23
16 Technical data
Input data
Nominal input voltage U
N
24 V AC/DC -15 % / +10 %
Typical input current I
N
140 mA AC
65 mA DC
Typical inrush current
2A (
Δ
t = 10 ms at U
N
)
< 40 mA (at U
N
/I
x
to S34)
Current consumption
< 50 mA (at U
N
/I
x
to S12)
0 mA (at U
N
/I
x
to S34)
Power consumption at U
N
3.36 W (AC)
1.56 W (DC)
Voltage at input/start and feedback circuit
24 V DC 15 % / +10 %
Max. permissible overall conductor resistance
∼
22
Ω
(Input and start circuits at U
N
)
Typical response time at U
N
< 65 ms (automatic start)
< 40 ms (manual start)
Typical starting time at U
N
< 65 ms (when controlled via A1)
Typical release time at U
N
< 45 ms (when controlled via S12)
< 200 ms (when controlled via A1)
Recovery time
1 s
Operating voltage display
1 x LED, green
Status display
2 x LEDs, green
Protective circuit
Surge protection Suppressor diode
Protection against polarity reversal for rated control
circuit supply voltage
Output data
Contact type
4 enabling current paths
1 signaling current path
Contact material
AgSnO
2
Minimum switching voltage
5 V AC/DC
Maximum switching voltage
250 V AC/DC (observe the load curve)
Limiting continuous current
6 A (N/O contact, pay attention to the derating)
6 A (N/C contact)
Maximum inrush current
20 A (
Δ
t
≦
100
ms)
Minimum inrush current
10 mA
Sq. Total current
(I
TH
)
2
=
(I
1
)
2
+ (I
2
)
2
+ … + (I
n
)
2
72 A
2
Interrupting rating (ohmic load) max.
144 W (24 V DC,
τ
= 0 ms)
288 W (48 V DC,
τ
= 0 ms)
110 W (110 V DC,
τ
= 0 ms)
88 W (220 V DC,
τ
= 0 ms)
1500 VA (250 V AC,
τ
= 0 ms)
Maximum interrupting rating (inductive load)
42 W (24 V DC,
τ
= 40 ms)
42 W (48 V DC,
τ
= 40 ms)
42 W (110 V DC,
τ
= 40 ms)
42 W (220 V DC,
τ
= 40 ms)
Switching capacity min.
50 mW
Summary of Contents for ESR5-NO-41-24VAC-DC
Page 1: ...Manual ESR5 NO 41 24VAC DC Safety relay 12 19 MN049009EN...
Page 4: ......