30
Commissioning and start-up
OperatiOnal manual
MN156001EN October 2015 www.eaton.com
2.
Touch Yes or No as applicable for the connected loads
and then touch Continue.
The unit asks if the connected load at the time of the CT
detection was capacitive (having a leading power factor)
or inductive (having a lagging power factor).
3.
Select the appropriate load type and touch Continue.
The CT configuration is displayed based on the answers
entered. The DPF value and Leading or Lagging can be
compared to an external meter to verify accuracy of the
results.
4.
Press OK.
The HMI returns to the CT Configuration screen.
5.
When the CTs are properly configured, touch OK.
System Mode Setup (HCU2 type)
Make the System Mode settings as follows:
Harmonic Modee:
When ON, the unit corrects harmonic
current.
Target THDe:
Set the target value to either THDi or THDv
based on application requirements.
PF Modee:
When ON, the unit corrects displacement power
factor. The default is set to a PF of 1.0.
Load Balancinge:
When ON, the three-phase currents at the
source have equal current on each phase.
System Mode Setup (EVI2 type)