34008236EN/AC - Page 12
2. Installation
HotSwap MBP module operation
UPS start-up with the HotSwap MBP module
1 - Check that the UPS is correctly connected to the
HotSwap MBP
module.
2 - Set switch
(53)
to Normal position.
3 - Start the UPS by pressing the ON/OFF button
(24)
on the UPS control panel.
The load is supplied by the UPS.
LED
(51)
"UPS ON - OK to switch" on the
HotSwap MBP
module goes ON.
HotSwap MBP module test
1 - Set switch
(53)
to Bypass position and check that the load is still supplied.
2 - Set switch
(53)
back to Normal position.
2.7 UPS connection without a FlexPDU or HotSwap MBP module
The
HotSwap MBP
module has a rotary
switch
(53)
with two positions:
Normal -
the load is supplied by the UPS,
Bypass -
the load is supplied directly by
the AC-power source.
Check that the indications on the name plate located on the back of the UPS correspond to the AC-power source
and the true electrical consumption of the total load.
1 -
Evolution S 1250 / S 1750 / 2000:
connect the UPS input socket (10) to the
AC-power source using the cable of the
protected equipment.
Evolution S 2500 / S 3000:
connect the
supplied cable
(31)
(250 V - 16 A) to the
socket
(10)
, then to the AC-power source.
2 - Connect the loads to the UPS using the
cables
(32)
.
It is preferable to connect the priority loads
to the four outlets marked
(9)
and the non-
priority loads to the four outlets marked
(8)
that can be programmed in pairs (1 and 2).
For the
Evolution S 2500 / S 3000
models,
connect any high-power devices to the 16
A outlet
(7)
.
To program shutdown of outlets
(8)
during
operation on battery power and thus
optimise the available backup time, the
EATON communication software is
required.
3 - Fit the connection securing system
(35)
that prevents the plugs from being pulled
out accidentally.
Note.
The UPS charges the battery as soon as it is connected to the AC-power source, even if button
(24)
is not
pressed.
Once the UPS is connected to the AC-power source, eight hours of charging are required before the battery can
supply the rated backup time.
By-p
ass
Normal
UPS ON - OK to switch
BY
P
ASS SWITCH
51
52
53
10
8
9
31
32
35
7
Summary of Contents for Evolution S 2500 RT 2U
Page 2: ...3400823600 AC ...
Page 4: ...34008236EN AC Page 2 ...
Page 24: ...34008236EN AC www eaton com ...
Page 26: ...34008236FR AC Page 2 ...
Page 46: ...34008236FR AC www eaton com ...
Page 48: ...34008236DE AC Page 2 ...
Page 68: ...34008236DE AC www eaton com ...
Page 70: ...34008236IT AC Page 2 ...
Page 90: ...34008236IT AC www eaton com ...
Page 92: ...34008236ES AC Page 2 ...
Page 112: ...34008236ES AC www eaton com ...
Page 114: ...34008236NL AC Page 2 ...
Page 134: ...34008236NL AC www eaton com ...
Page 135: ...www eaton com Pulsar Series ...
Page 136: ...34008236RU AC 2 ...
Page 137: ...34008236RU AC 3 ...
Page 138: ...34008236RU AC 4 ...
Page 139: ...34008236RU AC 5 ...
Page 140: ...34008236RU AC 6 ...
Page 141: ...34008236RU AC 7 ...
Page 142: ...34008236RU AC 8 ...
Page 143: ...34008236RU AC 9 ...
Page 144: ...34008236RU AC 10 ...
Page 145: ...34008236RU AC 11 ...
Page 146: ...34008236RU AC 12 ...
Page 147: ...34008236RU AC 13 ...
Page 148: ...34008236RU AC 14 ...
Page 149: ...34008236RU AC 15 ...
Page 150: ...34008236RU AC 16 ...
Page 151: ...34008236RU AC 17 ...
Page 152: ...34008236RU AC 18 ...
Page 153: ...34008236RU AC 19 ...
Page 154: ...34008236RU AC 20 ...
Page 155: ...34008236RU AC 21 ...
Page 156: ...34008236RU AC www eaton com ...
Page 157: ...3400823600 AC ...
Page 158: ...3400823600 AC www eaton com ...