background image

34008097EN/AE - Page 26

6. Appendices

6.1 Technical specifications

 

 

  

(1) 

EXB

 Module for 

EX 1000

 and 

EX 1500

.

(2) 

EXB

 Module for 

EX 1000 RT

 and 

EX 1500 RT

.

(3) Output power is 900 W in standard configuration, and 800 W as soon as 1 

EXB

 module is connected.

(4) Output power is 1350 W in standard configuration, and 1250 W as soon as 1 

EXB

 module is connected.

(5) Values for 20% / 33% / 66% / 100% of UPS output.

(6) Adjustable from 200 V to 250 V using the

 UPS Config 

software.

(7) Frequency-converter mode is programmable using the

 UPS Config 

software.

(8) Nominal values given for 230 V output voltage.

 

EX 700

EX 1000

EX 1000 RT

EX 1500

EX 1500 RT

EX EXB 

(1)

EX EXB RT 

(2)

Output power

700 VA / 630 W

1000 VA / 900 W

 

(3)

1500 VA / 1350 W

 

(4)

AC input power

 

Voltage

 

Frequency

 

Power factor

Single phase 100 / 120 / 140 V / 160 V / 184 V to 284 V 

(5)

50/60 Hz (autoselection)

> 0.95

Load output

 

Voltage

 

Frequency

 

Harmonic distortion (THDV)

 

Overload capacity

 

Current

Single phase 230 V ±3% 

(6)

50/60 Hz ±0.5% 

(7)

< 4% for linear load, < 6% for nonlinear load

102% continuous, 130% 12 s, > 130% 2 s

3 A 

(8)

4.3 A 

(8)

6.5 A 

(8)

Battery

2x12 V - 7 Ah,

sealed lead acid,

maintenance free

3x12 V - 7 Ah,

sealed lead acid,

maintenance free

3x12 V - 9 Ah,

sealed lead acid,

maintenance free

Two 3x12 V - 9 Ah 

strings, sealed 

lead acid, 

maintenance free

Environment

 

Noise level

 

Operating temperature range

 

Relative humidity

 

Leakage current

 

Storage temperature range

 

Altitude

< 38 dBA

0°C to 40°C

20% to 90% (without condensation)

< 1,1 mA

-25°C to 40°C

1000 m

Standards and certification

 

Safety

 

Performance

 

EMC

 

Markings

IEC/EN 62040-1-1, EN 60950-1 (RD)

IEC/EN 62040-3

EN 50091-2/IEC 62040-2 class B, IEC 61000-4-2/-3/-4/-6-8/-11, 

IEC 61000-3-2/-3

CE, TÜV/GS, UL, cUL, CB report

Summary of Contents for EX 1000

Page 1: ...www eaton com Installation and user manual EX 700 1000 1500 1000 RT 1500 RT EXB 1000 1500 EXB 1000 1500 RT Pulsar Series...

Page 2: ...34008097EN AE Page 2...

Page 3: ...ations concerning waste At the end of its service life the product must be transported to a processing centre for electrical and electronic waste Battery The product contains lead acid batteries that...

Page 4: ...tion Pictograms Important instructions that must always be followed Information advice help Visual indication Action Audio signal In the illustrations on the following pages the symbols below are used...

Page 5: ...with a HotSwap MBP module 13 HotSwap MBP module operation 14 2 8 UPS connection without a FlexPDU or HotSwap MBP module 14 3 Operation 3 1 Start up and normal operation 15 3 2 Operation on battery pow...

Page 6: ...s H x W x D in mm EX 700 242 x 153 x 440 EX 1000 242 x 153 x 440 EX 1000 RT 86 5 x 438 x 483 EX 1500 242 x 153 x 490 EX 1500 RT 86 5 x 438 x 483 EX EXB 242 x 153 x 440 EX EXB RT 86 5 x 438 x 483 Weigh...

Page 7: ...5 Connector for remote ON OFF and RPO Remote Power Off control 6 Connector for battery EXB module 7 Group of 3 programmable outlets for connection of equipment 8 Group of 3 outlets for connection of...

Page 8: ...module 1 3 Control panel 20 Load protected LED 21 Downgraded operation LED 22 Load not protected LED 23 Alphanumeric display 24 Escape cancel button 25 Scroll button 26 Enter confirm button 27 ON OFF...

Page 9: ...ion or optional 37 Mounting kit for 19 inch bays 38 2 supports for the upright position RT model only 39 FlexPDU module optional 40 Connection cable between FlexPDU module and UPS 41 NMC communication...

Page 10: ...n 2 3 Installation of the RT model in a rack It is advised to install the battery EXB module s at the lowest position in the rack then install the UPS above Follow steps 1 to 4 for module mounting on...

Page 11: ...cannot operate simultaneously Tower model 1 Connect the RS232 33 or USB 34 communication cable to the serial or USB port on the computer equipment 2 Connect the other end of the communication cable 33...

Page 12: ...4 secured by screws 2 Insert the communication card in the slot 3 Put the UPS cover back in place using the screws Pin 2 3 5 and 6 not used Pin 1 operation on automatic by pass Pin 4 user common Pin 7...

Page 13: ...Connect the input socket 56 on the HotSwap MBP module to the AC power source using the cable 44 supplied 2 Connect the UPS input socket 9 to the UPS Input 55 on the HotSwap MBP module using the cable...

Page 14: ...by the AC power source Check that the indications on the name plate located on the back of the UPS correspond to the AC power source and the true electrical consumption of the total load Tower model 1...

Page 15: ...ay be used to read UPS measurements AC input voltage operating mode battery capacity and UPS serial number If UPS personalisation is desired it is advised to enter the personalisation mode at this tim...

Page 16: ...ower Off allows a remote contact to be used to disconnect all the equipment connected to the UPS from the power supply Restarting the UPS requires manual intervention ROO Remote ON OFF allows remote a...

Page 17: ...closed start up of UPS UPS connected to the network and network energized Note local On Off control via button 27 has priority over the remote control order Contact open shut down of UPS To return to...

Page 18: ...ll button 25 several times until the personalisation menu is reached Press the Enter button 26 to access the different possibilities Finally confirm the selection by pressing the Enter button 26 again...

Page 19: ...battery power Enabled Disabled Automatic restart Enabled Disabled The UPS restarts automatically when AC power returns Energy savings Disabled Enabled When function enabled battery shuts down when po...

Page 20: ...evices Check the programmed overload level 6 LED 22 is ON the alphanumeric display indicates LOAD UNPROTECTED OUTPUT OVERLOAD The UPS is overloaded Devices connected to the UPS are fed directly by the...

Page 21: ...he wiring between the UPS and the HotSwap MBP module see section 2 6 13 The load is no longer supplied when the rotary switch 49 on the HotSwap MBP module is set to the Normal position The UPS is shut...

Page 22: ...battery two screws E Turn the connector F Pass the connector through the hole G Pull the plastic tab to remove the battery block and replace it Tower model A Put the front panel near the UPS B Disconn...

Page 23: ...fixing screws metal protection cover of the battery D Remove the metal protection cover of the battery E Pull the plastic tab to remove the battery block and replace it To ensure safety and high perfo...

Page 24: ...S control panel LED 51 UPS ON OK to switch goes OFF the UPS can now be disconnected and replaced Return to normal operation 1 Check that the UPS is correctly connected to the HotSwap MBP module 2 Star...

Page 25: ...ning centre To fully master operation of your EATON product and carry out level 1 servicing see our complete range of technical training courses available in both French and English For further inform...

Page 26: ...quency Power factor Single phase 100 120 140 V 160 V 184 V to 284 V 5 50 60 Hz autoselection 0 95 Load output Voltage Frequency Harmonic distortion THDV Overload capacity Current Single phase 230 V 3...

Page 27: ...y warning This is a battery voltage level indicating that battery power is low and that the user must take action in light of the imminent break in the supply of power to the load Normal AC input The...

Reviews: