34007776EN/AD - Page 12
2. Installation
HotSwap MBP-module operation
UPS start-up with the HotSwap MBP module
1 - Check that the UPS is correctly connected to the
HotSwap MBP
module.
2 - Set switch
(53)
to the Normal position.
3 - Start the UPS by pressing the ON/OFF button
(27)
on the UPS control panel.
The load is supplied by the UPS.
LED
(51)
"UPS ON - OK to switch" on the
HotSwap MBP
module goes ON.
HotSwap MBP-module test
1 - Set switch
(53)
to the Bypass position and check that the load is still supplied.
2 - Set switch
(53)
back to the Normal position.
2.7 UPS connection without a FlexPDU or HotSwap MBP module
The
HotSwap MBP
module has a rotary
switch
(53)
with two positions:
Normal
-
the load is supplied by the UPS,
Bypass
-
the load is supplied directly by
the AC-power source.
Check that the indications on the name plate located on the back of the UPS correspond to the AC-power source
and the true electrical consumption of the total load.
1 - Connect the supplied cable
(31)
(250 V -
16 A) to the socket
(10)
, then to the AC-
power source.
2 - Connect the loads to the UPS using the
cables
(32)
.
It is preferable to connect the priority loads
to the four outlets marked
(9)
and the non-
priority loads to the four outlets marked
(8)
that can be programmed in pairs (1 and 2).
Connect any high-power devices to the 16
A outlet
(7).
To program shutdown of outlets
(8)
during
operation on battery power and thus
optimise the available backup time, the
EATON communication software is
required.
3 - Fit the connection securing system
(35)
that prevents the plugs from being pulled
out accidentally.
Note.
The UPS charges the battery as soon as it is connected to the AC-power source, even if button
(27)
is not
pressed.
Once the UPS is connected to the AC-power source, eight hours of charging are required before the battery can
supply the rated backup time.
EX 3000 XL: at least one additionnal EXB battery module must be connected to the UPS because it does not have
internal batteries.
Refer to EXB battery module installation manual (doc n° 34008167) for further information about connections.
By-p
ass
Normal
UPS ON - OK to switch
BY
P
ASS SWITCH
51
52
53
10
8
9
31
32
35
7
Summary of Contents for EX 2200 RT 3U
Page 2: ...3400777600 AD...
Page 4: ...34007776EN AD Page 2...
Page 26: ...34007776EN AD www eaton com...
Page 28: ...34007776FR AD Page 2...
Page 50: ...34007776FR AD www eaton com...
Page 52: ...34007776DE AD Seite 2...
Page 74: ...34007776DE AD www eaton com...
Page 76: ...34007776IT AD Page 2...
Page 98: ...34007776IT AD www eaton com...
Page 100: ...34007776ES AD P gina 2...
Page 122: ...34007776ES AD www eaton com...
Page 124: ...34007776NL AD Pagina 2...
Page 146: ...34007776NL AD www eaton com...
Page 147: ...34003641FR AA Page 1 Pulsar Series...
Page 148: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ...XL...
Page 154: ......
Page 155: ......
Page 156: ......
Page 157: ......
Page 158: ...EX 3000 XL EXB EXB 34008167...
Page 159: ......
Page 160: ......
Page 161: ......
Page 162: ......
Page 163: ......
Page 164: ......
Page 165: ...12 13 14...
Page 166: ...EATON...
Page 167: ......
Page 168: ......
Page 169: ......
Page 170: ...D...
Page 171: ...3400777600 AD...
Page 172: ...3400777600 AD www eaton com...