background image

34008097EN/AE

 - Page 21

5. Maintenance

Troubleshooting a UPS equipped with the HotSwap MBP module

  

5.2 Batter -module replacement

Safety recommendations 

The battery can cause electrocution and high short-circuit currents. The following safety cautions are required 
before servicing the battery components:

 Remove watches, rings, bracelets and all other metal objects from the hands and arms,

 Use tools with an insulated handle.

Batter -module removal

  

  

Indication

Diagnostic

Correction

 

12

The load is no longer supplied when 

the rotary switch

 (49) 

on the 

HotSwap MBP 

module is set to the 

Bypass position.

  The protected devices are 

connected to the UPS output 

instead of to the 

HotSwap MBP

 

module.

  The AC-power cord is connected 

to the UPS input instead of to the 

HotSwap MBP

 module.

Check the wiring between the UPS 

and the 

HotSwap MBP

 module 

(see section 2.6).

13

The load is no longer supplied when 

the rotary switch

 (49) 

on the 

HotSwap MBP

 module is set to the 

Normal position.

  The UPS is shut down.

  The wiring between the UPS and 

the 

HotSwap MBP 

module is not 

correct.

  Start the UPS.

  Check the wiring between the 

UPS and the

 HotSwap MBP

 

module (see section 2.6).

14

The load is no longer supplied if AC-

power fails.

  The rotary switch

 (49) 

on the 

HotSwap MBP

 module is set to 

the Bypass position.

  The wiring between the UPS and 

the 

HotSwap MBP 

module is not 

correct.

  Set the rotary switch 

(49) 

on the 

HotSwap MBP 

module to the 

Normal position.

  Check the wiring between the 

UPS and the 

HotSwap MBP

 

module (see section 2.6).

If a fault leads to UPS shutdown, press the ON/OFF button

 (27) 

to clear the fault.

RT model

  

 

A

 

- Unscrew the left-hand side of the front 

panel (two screws).

B

 

- Remove the part.

  

 

C

 - Disconnect the battery block by 

separating the two connectors (never pull 

on the wires).

B

A

C

Summary of Contents for EX 700

Page 1: ...www eaton com Installation and user manual EX 700 1000 1500 1000 RT 1500 RT EXB 1000 1500 EXB 1000 1500 RT Pulsar Series...

Page 2: ...34008097EN AE Page 2...

Page 3: ...ations concerning waste At the end of its service life the product must be transported to a processing centre for electrical and electronic waste Battery The product contains lead acid batteries that...

Page 4: ...tion Pictograms Important instructions that must always be followed Information advice help Visual indication Action Audio signal In the illustrations on the following pages the symbols below are used...

Page 5: ...with a HotSwap MBP module 13 HotSwap MBP module operation 14 2 8 UPS connection without a FlexPDU or HotSwap MBP module 14 3 Operation 3 1 Start up and normal operation 15 3 2 Operation on battery pow...

Page 6: ...s H x W x D in mm EX 700 242 x 153 x 440 EX 1000 242 x 153 x 440 EX 1000 RT 86 5 x 438 x 483 EX 1500 242 x 153 x 490 EX 1500 RT 86 5 x 438 x 483 EX EXB 242 x 153 x 440 EX EXB RT 86 5 x 438 x 483 Weigh...

Page 7: ...5 Connector for remote ON OFF and RPO Remote Power Off control 6 Connector for battery EXB module 7 Group of 3 programmable outlets for connection of equipment 8 Group of 3 outlets for connection of...

Page 8: ...module 1 3 Control panel 20 Load protected LED 21 Downgraded operation LED 22 Load not protected LED 23 Alphanumeric display 24 Escape cancel button 25 Scroll button 26 Enter confirm button 27 ON OFF...

Page 9: ...ion or optional 37 Mounting kit for 19 inch bays 38 2 supports for the upright position RT model only 39 FlexPDU module optional 40 Connection cable between FlexPDU module and UPS 41 NMC communication...

Page 10: ...n 2 3 Installation of the RT model in a rack It is advised to install the battery EXB module s at the lowest position in the rack then install the UPS above Follow steps 1 to 4 for module mounting on...

Page 11: ...cannot operate simultaneously Tower model 1 Connect the RS232 33 or USB 34 communication cable to the serial or USB port on the computer equipment 2 Connect the other end of the communication cable 33...

Page 12: ...4 secured by screws 2 Insert the communication card in the slot 3 Put the UPS cover back in place using the screws Pin 2 3 5 and 6 not used Pin 1 operation on automatic by pass Pin 4 user common Pin 7...

Page 13: ...Connect the input socket 56 on the HotSwap MBP module to the AC power source using the cable 44 supplied 2 Connect the UPS input socket 9 to the UPS Input 55 on the HotSwap MBP module using the cable...

Page 14: ...by the AC power source Check that the indications on the name plate located on the back of the UPS correspond to the AC power source and the true electrical consumption of the total load Tower model 1...

Page 15: ...ay be used to read UPS measurements AC input voltage operating mode battery capacity and UPS serial number If UPS personalisation is desired it is advised to enter the personalisation mode at this tim...

Page 16: ...ower Off allows a remote contact to be used to disconnect all the equipment connected to the UPS from the power supply Restarting the UPS requires manual intervention ROO Remote ON OFF allows remote a...

Page 17: ...closed start up of UPS UPS connected to the network and network energized Note local On Off control via button 27 has priority over the remote control order Contact open shut down of UPS To return to...

Page 18: ...ll button 25 several times until the personalisation menu is reached Press the Enter button 26 to access the different possibilities Finally confirm the selection by pressing the Enter button 26 again...

Page 19: ...battery power Enabled Disabled Automatic restart Enabled Disabled The UPS restarts automatically when AC power returns Energy savings Disabled Enabled When function enabled battery shuts down when po...

Page 20: ...evices Check the programmed overload level 6 LED 22 is ON the alphanumeric display indicates LOAD UNPROTECTED OUTPUT OVERLOAD The UPS is overloaded Devices connected to the UPS are fed directly by the...

Page 21: ...he wiring between the UPS and the HotSwap MBP module see section 2 6 13 The load is no longer supplied when the rotary switch 49 on the HotSwap MBP module is set to the Normal position The UPS is shut...

Page 22: ...battery two screws E Turn the connector F Pass the connector through the hole G Pull the plastic tab to remove the battery block and replace it Tower model A Put the front panel near the UPS B Disconn...

Page 23: ...fixing screws metal protection cover of the battery D Remove the metal protection cover of the battery E Pull the plastic tab to remove the battery block and replace it To ensure safety and high perfo...

Page 24: ...S control panel LED 51 UPS ON OK to switch goes OFF the UPS can now be disconnected and replaced Return to normal operation 1 Check that the UPS is correctly connected to the HotSwap MBP module 2 Star...

Page 25: ...ning centre To fully master operation of your EATON product and carry out level 1 servicing see our complete range of technical training courses available in both French and English For further inform...

Page 26: ...quency Power factor Single phase 100 120 140 V 160 V 184 V to 284 V 5 50 60 Hz autoselection 0 95 Load output Voltage Frequency Harmonic distortion THDV Overload capacity Current Single phase 230 V 3...

Page 27: ...y warning This is a battery voltage level indicating that battery power is low and that the user must take action in light of the imminent break in the supply of power to the load Normal AC input The...

Reviews: