34008097EN/AE - Page 24
5. Maintenance
5.3 Maintenance on a UPS equipped with the HotSwap MBP module
RT model
The
HotSwap MBP
module makes
possible to service or even replace the
UPS without affecting the connected loads
(HotSwap function).
Maintenance:
1 - Set switch
(53)
to the Bypass position.
The red LED
(52)
on the
HotSwap MBP
module goes ON, indicating that the load
is supplied directly with AC power.
2 - Stop the UPS by pressing the ON/OFF
button
(27)
on the UPS control panel. LED
(51)
"UPS ON - OK to switch" goes OFF, the
UPS can now be disconnected and
replaced.
Return to normal operation:
1 - Check that the UPS is correctly
connected to the
HotSwap MBP
module.
2 - Start the UPS by pressing the ON/OFF
button
(27)
on the UPS control panel. LED
(51)
"UPS ON - OK to switch" on the
HotSwap MBP
module goes ON
(otherwise, there is a connection error
between the
HotSwap MBP
module and
the UPS).
3 - Set switch
(53)
to the Normal position.
The red LED
(52)
on the
HotSwap MBP
module goes OFF.
4 - The equipments are powered and
protected by the UPS.
By-p
ass
Normal
UPS ON - OK to switch
BY
P
ASS SWITCH
56
55
49
HotSwap MBP
50
54
53
51 52
44
43
8
7
9