INTERNAL BYPASS SWITCH INSTALLATION
Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide
S
164201403 Rev B
www.eaton.com/powerquality
50
60 Hz 208 Vac or 240 Vac Input - 120/208 Vac or 120/240 Vac Output
For 208 Vac, use only a BBM switch.
Figure 18. FE 4.3–18 kVA UPS with Internal Bypass Switch
Table 24. Minimum Recommended Circuit Breakers for 208 Vac or 240 Vac
208 Vac
240 Vac
Charger
4.3
kVA
5.3
kVA
7
kVA
10
kVA
12.5
kVA
18
kVA
4.3
kVA
5.3
kVA
7
kVA
10
kVA
12.5
kVA
18
kVA
Standard
25
30
40
60
80
110
20
25
35
50
70
100
10A
25
30
40
70
80
125
20
30
35
60
70
100
20A
30
35
40
70
90
125
25
35
35
60
80
110