36
Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05
Table 15. Additional Control Commands (Continued)
Additional Control Functions
Clear Logs
Press [CONTROL] —9 [ENTER] [ENTER]
Clears UPS History Log
Clear Alarms
Press [CONTROL] —0 [ENTER] [ENTER]
Clears any active alarm.
Silence active alarms
Press [CONTROL] —”.”
Silences the beeper on any active alarm.
If a new alarm becomes active the
beeper will sound.
77..33
EEnntteerr aa U
Usseerr P
Paassssw
woorrdd
Before you can change some parameter values, you must enter a user password through the Remote Control Display.
The user-level password is 000377. To enter the user-level password, follow these steps:
Table 16. Enter a User Password
Press This Key
Display Shows
[CLEAR]
EATON FX
[PROGRAM]
Password:
[0] [0] [0] [3] [7] [7]
Password: 000377
[ENTER]
Level: User
To clear the password, press [CLEAR] until Password Cleared appears on the remote control display.
NOTE
The password will automatically clear out of the system and have to be reentered if
there has been no activity for 10 minutes.
77..44
D
Diissppllaayyiinngg aanndd C
Chhaannggiinngg P
Paarraam
meetteerrss
The Remote Control Display allows you to display and change parameters by entering a user password.
Displaying a Parameter
The names of the first 11 parameters appear in blue on the top of the number keys. o display a parameter press
[DISPLAY], the parameter number, and [ENTER]. For example, to display parameter 0 (Time), follow these
steps:
Table 17. Display a Parameter
Press this Key
Display Shows
[DISPLAY]
Display:
[0]
Display: 0
[ENTER]
00 Time : 09:30:00