Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05
35
77..22
C
Chhaannggiinngg O
Oppeerraattiinngg M
Mooddeess
The Eaton FERRUPS FX UPS selects the appropriate operating mode automatically; however, there may be times when you
need to set the operating mode manually from the control panel.
The names of the Eaton FERRUPS FX control features are located in yellow at the bottom of the Remote
Control Display keys. You can change the operating mode by pressing the [CONTROL] button followed by the
number that describes the operating mode.
UPS Operating Mode Commands
Table 14. UPS Operating Mode Commands
Operating Mode
How to Select It
What It Means
Off
Press [CONTROL] —1 [ENTER] [ENTER]
The UPS does not provide power to your
equipment, but you can still use the
control panel if DC power is present. The
READY indicator is off.
Auto
Press [CONTROL] —2 [ENTER] [ENTER]
This is the normal operating mode for the
FX UPS. The UPS conditions AC input
power and provides the conditioned
power to your equipment. The AC LINE
and READY indicators should be
illuminated in this mode.
Line Condition
Press [CONTROL] —3 [ENTER] [ENTER]
The UPS is conditioning the AC input
power and providing the conditioned
power to your equipment, but if there is
power outage the UPS does not switch to
battery power. Instead, the UPS shuts
down output until AC input power is
available again. The READY indicator will
blink and the AC LINE indicator is on
when the UPS is in this mode.
Inv On
Press [CONTROL] —4 [ENTER] [ENTER]
The UPS converts battery power to AC
power for your equipment. It does not
charge the batteries. the On Batt
indicator is on. The READY indicator is
off.
Additional Control Commands
Table 15. Additional Control Commands
Additional Control Functions
Alarm
Press [CONTROL] —5 [ENTER] [ENTER]
Permanently enables and disables the
alarm beeper.
Chgr (Battery Charger)
Press [CONTROL] —6 [ENTER] [ENTER]
Enables and disables the UPS internal
charger.
User Test Alarm
Press [CONTROL] —8 [ENTER] [ENTER]
Initiates a User Test Alarm ( Can be
cleared by pressing [CONTROL] —8
[ENTER] [ENTER], or by pressing Press