Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05
49
14. If the voltage is correct turn the main breaker in the load distribution panel on and apply the load to the
UPS.
15.
If the UPS will not be operated immediately proceed to steps 17 — 21.
16. Turn the bypass switch back to the LINE position.
17. Press the UPS power button for 4 seconds so that the UPS turn off.
18. If your UPS has a DC switch, turn off the switch according to the UPS model:
•
FX3100 : The DC breaker is located on the back of the UPS. If you have an external battery cabinet
turn the DC breaker located on the front of the battery cabinet to the OFF position.
19. Turn the AC disconnect switch to the OFF position.
20. Reinstall the bypass switch and UPS front cover panels.
21. The equipment will not be protected by the UPS until you start up the UPS and turn the bypass switch to
the UPS position,
88..33
IInniittiiaall S
Sttaarrttuupp P
Paarraam
meetteerrss
Before programming the initial startup parameters, enter the user-level password.
The user-level password is 000377. To enter the user-level password, follow these steps:
Table 22. Enter a User Password
Press This Key
Display Shows
[CLEAR]
EATON FX
[PROGRAM]
Password:
[0] [0] [0] [3] [7] [7]
Password: 000377
[ENTER]
Level: User
To clear the password, press [CLEAR] until Password Cleared appears on the remote control display.
NOTE
The password will automatically clear out of the system and have to be reentered if
there has been no activity for 10 minutes.
Set the time and date using the remote control display.
The time parameter is parameter 0. To set the time in 24 hour format follow these steps:
Table 23. Setting the Time
Press This Key
Display Shows
[DISPLAY]
Display:
[0]
Display: 0
[ENTER]
00 Time: 11:30:20
[PROGRAM]
00 Pgm:
Enter the correct time (in 24-hour format). For example, if the time is 9:30 a.m.: