50
Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05
Press This Key
Display Shows
[9][3][0]
00 Pgm: 930
[ENTER]
00 Time 09:30:00
The date is parameter 10. To set the date, follow these steps:
Table 24. Setting the Date
Press This Key
Display Shows
[DISPLAY]
Display:
[1][0]
Display: 10
[ENTER]
10 Date: 01/01/19
[PROGRAM]
10 Pgm:
Enter the correct date (in MMDDYY format). For example, to enter June 4, 2019:
Press This Key
Display Shows
[0] [1] [0] [1] [1] [9]
10 Pgm: 010119
[ENTER]
10 Date 01/01/19
To ensure maximum battery runtime, the Eaton FX Ferrups UPS can be programmed for up to four FX battery
runtime options. To set the battery cabinet options you can program each cabinet type into parameters 95–98.
1.
Choose the type of battery cabinet you wish to use with the Eaton FX Ferrups UPS.
Table 25. External Battery Options Available To Program
Eaton Ferrups FX External Battery
Runtime Options
Battery Cabinet Type
Number to Program into the RCD
FXEBM01
N
1
FXEBM03
P
3
FXEBM04
P
4
FXEBM05
P
5
FXEBM06
P
6
NOTE
If there are four FXEBM01 battery cabinets connected to a FX 3100 UPS, then
parameters 95,96,97,98 all should be programmed to a value of 1.
2.
Program the first battery cabinet type into parameter 95. See the example below.