Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05
51
Table 26. Program The External Battery Cabinet Option
First Battery Cabinet Option Type
Press This Key
Display Shows
[DISPLAY]
Display:
[9] [5]
Display: 95
[ENTER]
95 EBM 1: Default 0) NONE
[PROGRAM]
95 Pgm:
New Value
95 Pgm: 1) FXEBM01
[ENTER]
95 EBM 1 : 1) FXEBM01
*0 is the default setting for parameters 95–98*
3.
Repeat the steps above for parameters 96 through 98 if more than one Eaton FX Ferrups battery cabinet is
to be used.
Setup for Using a Custom Non Eaton Ferrups FX Battery Configuration
To set the UPS for a customer supplied battery configuration the following parameters must be set with the
user level password:
Table 27. Enter a User Password
Press This Key
Display Shows
[CLEAR]
EATON FX
[PROGRAM]
Password:
[0] [0] [0] [3] [7] [7]
Password: 000377
[ENTER]
Level: User
Set the parameter 90 with the RCD to allow the use of a customer supplied custom battery configuration:
Press This Key
Display Shows
[DISPLAY]
Display:
[90]
Display: 90
[ENTER]
90 Custom Batt: 0
[PROGRAM]
90 Pgm: 1 (Yes)
Program in the battery amp hour capacity of the batteries being used with the UPS:
Press This Key
Display Shows
[DISPLAY]
Display: