76
Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05
Table 36. Bypass Switch Dimensions and Weight
Model
Height (Inches)
Width (Inches)
Depth (Inches)
Weight (Pounds)
BPEFXMBB02
17
12
7
20lbs
BPEFXMBB04 and
BPEFXMBB05 (Make
Before Break)
18
16
9
30lbs
BPEFXBBM04 and
BPEFXBBM05 (Break
Before Make)
18
16
9
33lbs
1122..55
B
Baatttteerryy C
Caabbiinneett W
Weeiigghhttss aanndd D
Diim
meennssiioonnss
Table 37. Battery Cabinet Dimensions
Dimensions H X W X D
N Cabinet
P Cabinet
37” x 19” x 32”
49” X 15’ X 32”
Table 38. Battery Cabinet Weight
Eaton FERRUPS FX Battery
Option
Cabinet Type
Battery Type
Weight
Type “N” Battery Cabinet
With No Batteries
-
-
142 lbs
Type “P” Battery Cabinet With
No Batteries
-
-
175 lbs
FXEBM01
N
PWHR12280W4FR (12 Volt) X
8
630 lbs
FXEBM03
P
PWHR12280W4FR (12 Volt) X
12
910 lbs
FXEBM04
P
PWHR12330W4FR (12 Volt) X
12
1015 lbs
FXEBM05
P
PWHR12620W4FR (12 Volt) X
12
1430 lbs
FXEBM06
P
SWU585–12FR (12 Volt) X 12
1465 lbs
1122..66
B
Baatttteerryy
Table 39. UPS Runtimes
Eaton Ferrups FX 3100 Runtimes
FX EBM Option
Runtime
Ah Rating / DC Voltage
Full Load
Half Load
**Standard Internal Batteries Only**
14 Minutes
35 Minutes
33Ah/1 String/48V
**FXEBM01 w/o UPS Internal
Batteries**
86 Minutes
242 Minutes
70Ah/2 Strings/48V