2
Installation and User manual for the
conventional range of fire panels
EATON
www.eaton.com
Technical Data
PR000-00-513-05
Effective
January
201
8
General
Installation
Please read the following instructions before installing and wiring
the fire alarm panel .
This range of panels is EN54 parts 2 and 4 certified and have been
designed to comply with BS5839 part 1:2002 installations .
The panels have two optional features:
FIRE ALARM DEVICES: (EN54 part 2 clause 7 .8)
TEST CONDITION: (EN54 part 2 clause 10 .0)
In common with all electrical equipment the panel should be
installed in a clean, dry, well ventilated area, not in direct sunlight
and avoiding cold areas where possible . Note, temperatures in
excess of 40°C will affect the panel operation . The panel should be
located away from any potential hazard, in a position where it is
readily accessible to authorised staff and the fire services .
Ideally on the perimeter of a building near a permanent entrance .
Figure 1. Panel installation
Mount the panel, using pre drilled screw positions, to the wall .
This will prevent any possible brick dust contamination of the
panel internal circuitry .
Fit a 20mm gland to all cable entry points in use .
Wiring
Mains power supply
The mains supply should be exclusive to the fire alarm as detailed
in BS5839 part 1 . It is recommended that a double pole fused spur
unit is used and marked “FIRE ALARM DO NOT SWITCH OFF”,
this should be for the sole use of the fire alarm .
Within the panel, the mains supply should be isolated from the
zone and alarm line wiring and should be connected to the termi-
nal block marked MAINS .
Figure 2. Mains power connection
Battery connection
The 2 & 4 zone panel requires a single battery (supplied)
*Note: For -NB variants, purchase batteries seperately
2 and 4 zone panels: 1x12v 3 .2Ah
Connect the red battery wire to the red battery terminal (+) .
Connect the black battery wire to the black battery terminal (-) .
Figure 3. Battery Connection location
Figure 4. Battery Connection schematic