background image

4

Installation and User manual for the 

conventional range of fire panels 

  

EATON

 www.eaton.com

Technical Data 

PR000-00-513-05

Effective 

January 2018

Sounder Wiring

The standard 2 and 4 zone fire alarm control panels have two 

separately protected, line monitored, sounder circuits for use with 

polarised and suppressed bells, sounders, strobes, relays etc .
The 8 zone fire alarm control panel has four separately protected, 

line monitored, sounder circuits for use with polarised and 

suppressed bells, sounders, strobes, relays etc .
The wiring for each sounder circuit is to be a parallel circuit with 

the 6K8, end of line resistor (EOLR), fitted at the end of the 

installed sounder circuit wiring . No ‘spurs’ or ‘tees’ permitted .

Fault/Fire Relay (2-zone & 4-zone)

The 2 & 4 zone panels have one auxiliary relay fitted that provides 

a fused volt-free set of change over contacts . These contacts are 

not monitored .
The relay has been designed to ‘fail-safe’, so that in the event of 

total loss of power the relay contacts will be active .
The auxiliary contacts are fuse protected at 5 Amps (F2) and rated 

at 30V dc .
The wiring connections can be found on the main board and are 

labelled ‘Auxiliary Circuit’ .
The auxiliary relay is factory configured as a fault relay but can be 

configured to operate as a general fire relay using LK1 (Figure 7) . 

This can be found on the display PCB and will need to be removed 

from the door in order to gain access to it .

LK1

Mode

Panel 

Healthy

Panel in 

Fault

Panel in 

Fire

Position 

AB

Fault 

Relay

Continuity 

between C 

and P2

Continuity 

between C 

and P2

Continuity 

between C 

and P1

Position 

BC

Fire Relay Continuity 

between C 

and P2

Continuity 

between C 

and P1

Continuity 

between C 

and P2

Figure 7.  2 & 4 zone panel Auxiliary relay

CAUTION

POWER DOWN THE FIRE PANEL BEFORE YOU CHANGE ANY 

RELAY SETTINGS

J1

Mode

Panel 

Healthy

Panel in 

Fault

Panel in 

Fire

Not Fitted

Fault 

Relay

Continuity 

between C 

and N/C

Continuity 

between C 

and N/C

Continuity 

between C 

and N/O

Link Fitted Fire Relay Continuity 

between C 

and N/C

Continuity 

between C 

and N/O

Continuity 

between C 

and N/C

Figure 8. Class change input

Summary of Contents for FX2202CPD

Page 1: ...tallation and User manual for the conventional range of fire panels 2 and 4 zone panels Contents General 2 Wiring 2 Commissioning the system 5 Walk test facility 5 User Information 6 Self check detect...

Page 2: ...double pole fused spur unit is used and marked FIRE ALARM DO NOT SWITCH OFF this should be for the sole use of the fire alarm Within the panel the mains supply should be isolated from the zone and ala...

Page 3: ...Each zone circuit is supplied with an End of Line Monitor unit EOLM 1 All zone circuits must be terminated with an EOLM 1 connected at the end of the installed zone wiring taking care to observe the c...

Page 4: ...y between C and P2 Continuity between C and P1 Continuity between C and P2 Figure 7 2 4 zone panel Auxiliary relay CAUTION POWER DOWN THE FIRE PANEL BEFORE YOU CHANGE ANY RELAY SETTINGS J1 Mode Panel...

Page 5: ...he last call point in each zone operates correctly by using the supplied call point test key Reset the panel after each activation Fit all the detectors a zone at a time and check the panel shows heal...

Page 6: ...resets detectors and resets control relays Enter access code level 2 Then press button followed by Ensure any smoke still in the activated detector is blown clear as the control panel will activate b...

Page 7: ...under LED turns off Push button to confirm enable sounders Self check detectors This function is no longer available on new panels however it may be available on existing panels Detector LED function...

Page 8: ...d batteries are no longer available as original equipment Carry out battery load test by disconnecting the mains supply and check the battery is capable of supplying the alarm sounder load by activati...

Page 9: ...ttent Internal buzzer steady Fire General Fault Disable Power On Charger fault System fault Disable Fault zone Disable Fault counter cct Test Buzzer Normal condition Zone wiring open short Zone disabl...

Page 10: ...V dc Fuse 5 Amp Glass Fuse F2 Located Main board Mode Configurable as Fire or Fault Relay Fire Relay Type N A Rating N A Fuse N A Located N A Mode N A Auxiliary Output V 24V dc Imax 30 mA Fuse Polyswi...

Page 11: ...ecifications cont PSE Specification 2 Zone 4 Zone Mains Voltage V ac 230 10 15 Number of Batteries 1 Voltage V 12 Capacity aH 3 2 Standby Time 24 hour standby 30 minute alarm EOLM 1 Specification Oper...

Page 12: ...Data PR000 00 513 04 Effective January 2018 Installation and User manual for the conventional range of fire panels Eaton is a registered trademark All other trademarks are property of their respectiv...

Reviews: