Installation and User manual for the 

conventional range of fire panels 

  

EATON

 www.eaton.com

Repeater panel

The 8 zone panel has a RS485 repeater output as standard . Some 

2 and 4 zone panels have been factory configured with a repeater 

panel as a special order, however this facility is no longer provided 

for new panels .
The repeater panel has been designed to provide a cost effective 

installation solution, requiring only two interconnecting wires from 

the master panel . Several repeater panels can be installed from 

the master panel by ‘cascading’ each repeater panel, again only 

two interconnecting wires are required between each repeater 

panel .
As each repeater has its own mains supply and standby battery 

the main panel standby time is not affected by the number of 

repeater panels installed .
The repeater panel is suitable for up to 8 zones and displays all the 

same indications as the main panel, but with the addition of an 

indicator test and mute buzzer facility .

Repeater panel wiring

Connect the repeater, RS485 TX+ and Tx- terminals of the main-

panel, to the repeater panel positive and negative input terminals 

(Figure 11) .

Main Panel Repeater Panel

TX+ to +ve input terminal

TX- to -ve input terminal

Figure 9. Repeater panel connections

The minimum required cable size is 1mm

2

 with a maximum length 

of 2km .

Installation check

With the EOLM-1’s and EOL resistors fitted in the main panel, 

connect the mains supply and battery . Check the green power on 

LED is lit and that no other indicators are lit .
Check the panel operates correctly by entering the access 

code (3112), then silence, then reset, check all indicators show 

momentarily .
Check each zone and alarm line for open and short circuit fault 

monitoring .

Zone circuits

Disconnect the mains and battery supply, wire in the zone circuits, 

one at a time, with the EOLM-1 transferred to the end of the zone 

(check polarity) but with no detectors fitted .
Power up the panel by connecting the mains supply and battery . 

Check that the last call point in each zone operates correctly by 

using the supplied call point test key . Reset the panel after each 

activation .
Fit all the detectors (a zone at a time) and check the panel shows 

healthy . If there is a problem (zone fault showing) check the faulty 

circuit for continuity, correct polarity and polarity of the base 

diodes .

CAUTION

DO NOT USE A HIGH VOLTAGE TESTER WHEN WIRING IS 

CONNECTED TO ANY ELECTRONIC EQUIPMENT.

Sounder circuits

Disconnect the mains and battery supply . Wire in the sounder 

circuits, one at a time, transferring the end of line resistor to the 

end sounder/bell on each circuit .
Power up the panel as before and verify that no faults show .
If there is a fault indication check the affected circuit for short 

circuit, continuity and polarity .

CAUTION

DO NOT USE A HIGH VOLTAGE TESTER WHEN WIRING IS 

CONNECTED TO ANY ELECTRONIC EQUIPMENT.

Commissioning the system

Assuming that the installation instructions and installation checks 

have been carried out successfully the fire alarm system is ready 

for commissioning .
Each detector and call point should be tested in turn to ensure that 

it operates, indicates the correct zone fire LED and operates the 

alarm output correctly, ensuring all sounders/bells operate .

Walk test facility

A walk test function has been included in this range of panels to 

enable one person (electrical contractor or installer) to test the 

fire detection system without an assistant . This function is for the 

sole use of the electrical contractor or installer and not for normal 

operational use .
The walk test facility access code is located inside the fire detec-

tion control panel .
Once the walk test code has been correctly entered the ‘test in 

progress’ indicator will show and the buzzer will pulse, this sets a 

time window of 10 minutes .
If a detector or call point is triggered within this period the sound-

ers will operate for a short time then the system will automatically 

reset ready for the next call point or detector activation .
If a detector or call point is not operated within the 10 minute 

period then the system will automatically reset and return to 

normal operation .
The walk test facility can be terminated at any time during test by 

pressing the ‘reset’ button .

Summary of Contents for FX2202CPD

Page 1: ...tallation and User manual for the conventional range of fire panels 2 and 4 zone panels Contents General 2 Wiring 2 Commissioning the system 5 Walk test facility 5 User Information 6 Self check detect...

Page 2: ...double pole fused spur unit is used and marked FIRE ALARM DO NOT SWITCH OFF this should be for the sole use of the fire alarm Within the panel the mains supply should be isolated from the zone and ala...

Page 3: ...Each zone circuit is supplied with an End of Line Monitor unit EOLM 1 All zone circuits must be terminated with an EOLM 1 connected at the end of the installed zone wiring taking care to observe the c...

Page 4: ...y between C and P2 Continuity between C and P1 Continuity between C and P2 Figure 7 2 4 zone panel Auxiliary relay CAUTION POWER DOWN THE FIRE PANEL BEFORE YOU CHANGE ANY RELAY SETTINGS J1 Mode Panel...

Page 5: ...he last call point in each zone operates correctly by using the supplied call point test key Reset the panel after each activation Fit all the detectors a zone at a time and check the panel shows heal...

Page 6: ...resets detectors and resets control relays Enter access code level 2 Then press button followed by Ensure any smoke still in the activated detector is blown clear as the control panel will activate b...

Page 7: ...under LED turns off Push button to confirm enable sounders Self check detectors This function is no longer available on new panels however it may be available on existing panels Detector LED function...

Page 8: ...d batteries are no longer available as original equipment Carry out battery load test by disconnecting the mains supply and check the battery is capable of supplying the alarm sounder load by activati...

Page 9: ...ttent Internal buzzer steady Fire General Fault Disable Power On Charger fault System fault Disable Fault zone Disable Fault counter cct Test Buzzer Normal condition Zone wiring open short Zone disabl...

Page 10: ...V dc Fuse 5 Amp Glass Fuse F2 Located Main board Mode Configurable as Fire or Fault Relay Fire Relay Type N A Rating N A Fuse N A Located N A Mode N A Auxiliary Output V 24V dc Imax 30 mA Fuse Polyswi...

Page 11: ...ecifications cont PSE Specification 2 Zone 4 Zone Mains Voltage V ac 230 10 15 Number of Batteries 1 Voltage V 12 Capacity aH 3 2 Standby Time 24 hour standby 30 minute alarm EOLM 1 Specification Oper...

Page 12: ...Data PR000 00 513 04 Effective January 2018 Installation and User manual for the conventional range of fire panels Eaton is a registered trademark All other trademarks are property of their respectiv...

Reviews: