Installation and User manual for the 

conventional range of fire panels 

  

EATON

 www.eaton.com

Technical Data 

PR000-00-513-05

Effective 

January 2018

User Information

There are 2 access codes used by the control panel: 

access code level 2 - client code (3112)

and

access code level 3 - engineers code

These codes are displayed on the rear of the front panel .
The access level 2 code is also shown on the panel key fob .
Level 2 access permits the following functions:

Silence alarm

Evacuate

Enable and disable zones

Enable or disable sounders

System reset

The access code (level 2 or 3) is enabled by pressing the five 

control panel front buttons in the correct sequence .

①②③④⑤

An audible signal indicates that the access code keyed in is 

correct .

Mute buzzer

Silences control panel’s internal buzzer .

Enter access code level 2, then press button 

Silence alarm

Silences external sounders and mutes internal buzzer

Enter access code level 2 . 

Then press button 

 followed by

Reset after fire alarm activation

Silences buzzer, resets the panel indicators, resets detectors and 

resets control relays .

Enter access code level 2 .

Then press button          followed by       

Ensure any smoke still in the activated detector is blown clear, as 

the control panel will activate back into alarm should any smoke 

remain .

Reset panel without a fire activation

(e .g . to reset a fault indication when fault latch facility set)
Silences buzzer, resets the panel indicators and resets faults relay .

Enter access code level 2

Then press button          followed by 

Evacuate

Operates the control panel’s sounder circuits and fire relay(s)

Enter access code level 2, then press button

To silence the alarm during evacuate period

Enter access code level 2

Then press button        followed by 

Disable zone

Isolates required detection zone from the system

Enter access code level 2, then press button 

The yellow LED of the zone 1 will light and the internal buzzer will 

pulse rapidly .
Push button         several times until both the required zone and 

disabled yellow LEDs are lit .
Push button         to disable the indicated zone .
Repeat this procedure to disable further zones .
The internal buzzer will pulse at a slow rate and the disabled and 

zone disabled LEDs will remain lit .
To silence the internal buzzer

Enter access code level 2, then press button

Summary of Contents for FX2202CPD

Page 1: ...tallation and User manual for the conventional range of fire panels 2 and 4 zone panels Contents General 2 Wiring 2 Commissioning the system 5 Walk test facility 5 User Information 6 Self check detect...

Page 2: ...double pole fused spur unit is used and marked FIRE ALARM DO NOT SWITCH OFF this should be for the sole use of the fire alarm Within the panel the mains supply should be isolated from the zone and ala...

Page 3: ...Each zone circuit is supplied with an End of Line Monitor unit EOLM 1 All zone circuits must be terminated with an EOLM 1 connected at the end of the installed zone wiring taking care to observe the c...

Page 4: ...y between C and P2 Continuity between C and P1 Continuity between C and P2 Figure 7 2 4 zone panel Auxiliary relay CAUTION POWER DOWN THE FIRE PANEL BEFORE YOU CHANGE ANY RELAY SETTINGS J1 Mode Panel...

Page 5: ...he last call point in each zone operates correctly by using the supplied call point test key Reset the panel after each activation Fit all the detectors a zone at a time and check the panel shows heal...

Page 6: ...resets detectors and resets control relays Enter access code level 2 Then press button followed by Ensure any smoke still in the activated detector is blown clear as the control panel will activate b...

Page 7: ...under LED turns off Push button to confirm enable sounders Self check detectors This function is no longer available on new panels however it may be available on existing panels Detector LED function...

Page 8: ...d batteries are no longer available as original equipment Carry out battery load test by disconnecting the mains supply and check the battery is capable of supplying the alarm sounder load by activati...

Page 9: ...ttent Internal buzzer steady Fire General Fault Disable Power On Charger fault System fault Disable Fault zone Disable Fault counter cct Test Buzzer Normal condition Zone wiring open short Zone disabl...

Page 10: ...V dc Fuse 5 Amp Glass Fuse F2 Located Main board Mode Configurable as Fire or Fault Relay Fire Relay Type N A Rating N A Fuse N A Located N A Mode N A Auxiliary Output V 24V dc Imax 30 mA Fuse Polyswi...

Page 11: ...ecifications cont PSE Specification 2 Zone 4 Zone Mains Voltage V ac 230 10 15 Number of Batteries 1 Voltage V 12 Capacity aH 3 2 Standby Time 24 hour standby 30 minute alarm EOLM 1 Specification Oper...

Page 12: ...Data PR000 00 513 04 Effective January 2018 Installation and User manual for the conventional range of fire panels Eaton is a registered trademark All other trademarks are property of their respectiv...

Reviews: