Explosion-protected plugs and sockets 16 A, GHG 511

GB

1.1  Plug and socket GHG 511

ATEX type examination certificate:

PTB 99 ATEX 1039

Marking acc. to 94/9/EC  and standard::
EN 60079-0

 II 2 G Ex de [ia] IIC T6/T5 
 II 2 D Ex tD A21 IP66 T80°C

IECEx type examination certificate:

IECEx BVS 12.0027

Category of application:
IEC60079-0

Ex de IIC T5/T6 Gb 

Ex tb IIIC T80°C Db IP66

Rated voltage:
GHG 511 -  

3-pole 

GHG 511 -  

4-pole 

GHG 511 -  

5-pole

up to 415 V, 50/60 Hz 

up to 690 V, 50/60 Hz 

up to 500 V, 50/60 Hz

Rated current:

max. 16 A

Back-up fuse:
without thermal protection

max. 25 A

with thermal protection

max. 35 A gL

Switching capacity AC 3, 3-pole:

250 V/16 A

Switching capacity AC 3, 4-pole:

400 V/16 A

Switching capacity AC 3, 5-pole:

400 V/16 A

Perm. ambient temperature: 

(catalogue version, special versions permit deviating 

temperatures.)

-20° C to +40° C

Perm. storage temperature in original packing: -20° C to +40° C
**Protection category acc. to EN/IEC 60529

with closed and secured hinged cover as well 

as combinations properly plugged together

IP 66 (catalogue version)

Insulation class acc. to EN/IEC 61140:

II - is complied with by the devices

Cable entry:

(catalogue version)

wall socket

2x blanking plug M25

Supply terminals:

  Cross section 

Stripped wire length

terminals

  2 x 1,5  - 10 mm²  

     16 mm

Test torques:
Cover screws

3.0 Nm

Terminals

4.0 Nm

Weight:

(catalogue version)

wall socket      4/5-pole         GHG 511 45

approx. 5.4 kg

Auxiliary contact:
Rated voltage:

250 V AC

Switching capacity:

AC: 5 A
DC: 0.03 A

Technical data

2   Safety instructions

This  „Annex to operating instructions“  

GHG 5107001P0012 is  

only for use with the original operating 
instructions  
”GHG 510 7001 P0001“. The GHG 511 plugs 
and sockets are not suitable for Zone 0 and 
Zone 20 hazardous areas.

Observe the national safety rules and 
regulations for prevention of accidents as 
well as the safety instructions included in 
these operating instructions and set in 
italics the same as this text!

4   Use/Properties

The GHG 511 plugs and sockets are used for 
the power supply of local controls with varying 
locations, as well as of electrical installations, 
mobile machinery and driving gear in hazardous 
areas. 
The plugs and sockets can also be used in a 
”normal industrial area“. 
The low-voltage plugs and sockets GHG 511 
are fitted with a load switch and can be used 
up to max. 16 A (see technical data). 
The plugs and sockets can generally be used 
for the voltage range laid down in  
IEC/EN 60309 (e.g. UN 400V that corresponds 
to the voltage range 380-415V).

The apparatus connected to the plug shall 
be suitable for the applied mains voltage. 

3   Field of application

The plugs and sockets GHG 511 are suitable 
for use in Zone 1, 2 and 21, 22 hazardous 
areas acc. to IEC/EN 60079-10-1 and  
IEC/EN 60079-10-2!

The enclosure materials employed, including 
the exterior metal parts, are made of high-
quality materials which ensure a corrosion 
protection and resistance to chemical sub-
stances corresponding to the requirements in 
a “normal industrial atmosphere”:

    

- impact resistant polyamide 

    

- glass-fibre reinforced polyester 

    

- special steel AISI 316 L

In case of use in an extremely aggressive 
atmosphere, please refer to manufacturer.

 

Wall mounting bracket

 side

 top/bottom

Fig. 1

Summary of Contents for GHG 511

Page 1: ...G 511 Explosion protected plug and socket system 16 A 3 pole 4 pole 5 pole GHG 511 Fiches et prises de 16 A 3 p les 4 p les 5 p les pour atmosph res explosives GHG 511 Betriebsanleitung Operating inst...

Page 2: ...ions 7 3 Conformity with standards 8 4 Field of application 8 5 Use Properties 8 6 Installation 8 6 1 Mounting 9 6 2 Opening the device Electrical connection 9 6 3 Cable entries KLE blanking plugs 9 6...

Page 3: ...5 Ex tD A21 IP 66T 80 C Flanschsteckdose GHG 511 8 Ex db eb IIC IIB Gb Ex tb IIIC Db Bemessungsspannung GHG 511 3 polig bis 415 V 50 60 Hz GHG 511 4 polig bis 690 V 50 60 Hz GHG 511 5 polig bis 690 V...

Page 4: ...ng zu sichern Das Stecken undTrennen des Steckers von der Steckdose ist nur im ausgeschalteten Zustand m glich Nach dem Einschalten der Steckdose wird um die Schutzart gem Typenschild auch mit gesteck...

Page 5: ...das Griffst ck eindrehen Alle Schrauben und oder Muttern der An schlussklemmen auch die der nicht benutzten sind fest anzuziehen Bei berm igem Anziehen kann der Anschluss beeintr chtigt oder besch di...

Page 6: ...sicherstellen oder geeignete Schutzma nahmen ergreifen Die erforderlichenWartungsintervalle sind anwendungsspezifisch und daher in Abh ngig keit von den Einsatzbedingungen vom Betreiber festzulegen Im...

Page 7: ...x de ia II CT6 bzw T5 Ex tD A21 IP 66T 80 C Flange socket GHG 511 8 Ex db eb IIC IIB Gb Ex tb IIIC Db Rated voltage GHG 511 3 pole up to 415 V 50 60 Hz GHG 511 4 pole up to 690 V 50 60 Hz GHG 511 5 po...

Page 8: ...plug can be pushed into the socket and pulled out of it only whilst the socket is switched off In order to ensure the socket s type of protection acc to the type label also with the plug being inserte...

Page 9: ...tive contacts When reassembling the flange screws shall be screwed into the body sleeve with a maximum test torque of 1 Nm All screws and or nuts of the supply terminals also of those remaining vacant...

Page 10: ...s depend on the specific application and will therefore have to be determined by the user dependent on the conditions of use When servicing the plugs and sockets parti cularly those parts that are dec...

Page 11: ...Prise bride GHG 511 8 Ex db eb IIC IIB Gb Ex tb IIIC Db Tension nominale GHG 511 3 p les jusqu 415 V 50 60 Hz GHG 511 4 p les jusqu 690 V 50 60 Hz GHG 511 5 p les jusqu 500 V 50 60 Hz Fiche GHG 543 2...

Page 12: ...bloqu e avec l anneau ba onnette La fiche ne peut tre enfich e dans la prise ou retir e de celle ci que lorsque la prise est mise hors circuit Afin d assurer le mode de protection selon la plaque sign...

Page 13: ...exion aussi celles des bornes non utilis es doivent tre serr es fond Afin de maintenir le mode de protection contre l explosion le raccordement des conducteurs doit se faire tr s soigneusement Les bor...

Page 14: ...rvice requis d pendent de l emploi sp cifique et devront donc tre fix s par l utilisateur en tenant compte des condi tions d exploitation Lors de l entretien des appareils surtout les composants qui s...

Page 15: ...liaire GHG 511 543 Ansicht 1 View 1 Voir 1 Ansicht 2 View 2 Voir 2 2 1 Schaltschema Switching operation m canisme de commutation AnschlussbildWand Flanschsteckdose GHG 511 Contact arrangementWall Flan...

Page 16: ...nwand Inner wall of enclosure Paroi interne de l enveloppe 110 130V gelb yellow jaune 220 250V blau blue bleu 220 250V blau blue bleu 380 415V rot red rouge 500V schwarz black noir GHG 511 3 pol PE 50...

Page 17: ...s in mm Dimensions en mm X Befestigungsma e X fixing dimensions X dimensions de fixation 2 pol PE 3 pol PE 3 p l N PE Flanschsteckdose Flange socket Prise bride 2 pol p l PE Flanschsteckdose Flange so...

Page 18: ...e GHG 543 23 2 pol p l PE Stecker Plug Fiche GHG 531 7 4 5 pol p l PE Stecker Plug Fiche GHG 511 4 4 5 pol p l PE Stecker Plug Fiche GHG 511 43 2 pol p l PE Kupplung Coupler Prolongateur 2 pol p l PE...

Page 19: ...19 Notizen Notes Remarques...

Page 20: ...er Crouse Hinds CEAG estas instrucciones de servicio en otro idioma de la Union Europea EST Seda kasutusjuhendit oma riigikeeles v ite k sida oma riigis asuvast asjaomasest Cooper Crouse Hindsi CEAG e...

Page 21: ...plugs and sockets 16 A 4 pole and 5 pole GHG 511 stainless steal Fiche et prise de 16 A 4 p les et 5 p les pour atmosph res explosives GHG 511 acier inoxydable GHG 510 7001 P0012 D GB F a CROUSE HIND...

Page 22: ...ns contact auxiliaire avec contact auxiliaire GHG 511 3 pol PE 50 60Hz 380 415V rot GHG 511 4 pol PE 50 60Hz 220 250V blau 690V schwarz 500V schwarz 380 415V rot 220 250V blau 690V schwarz 500V schwar...

Page 23: ...eitshinweise Dieser Anhang zur Betriebsanleitung GHG 510 7001 P0012 ist immer mit der Betriebsanleitung GHG 510 7001 P0001 zu verwenden Dort aufgef hrte Hinweise sind zu beachten Die Steckvorrichtunge...

Page 24: ...nter Ber cksichti gung einschl giger Vorschriften anzuschlie en Der Zusammenbau erfolgt nach dem Kabel anschluss in umgekehrter Reihenfolge Die minimal und maximal anschlie baren Leiterquerschnitte so...

Page 25: ...instructions This Annex to operating instructions GHG 5107001P0012 is only for use with the original operating instructions GHG 510 7001 P0001 The GHG 511 plugs and sockets are not suitable for Zone...

Page 26: ...crews and or nuts of the supply terminals also of those remaining vacant shall be tightened down The conductors shall be connected with special care in order to maintain the explosion category The sup...

Page 27: ...utilis e qu avec le mode d emploi original GHG 510 7001 P0001 Les fiches et prises du type GHG 511 pour atmosph re explosive ne sont pas appropri es la zone 0 et zone 20 Respectez les prescriptions n...

Page 28: ...tenant compte des r glements respectifs les conducteurs d ment d nud s des c bles sont raccord s Apr s le raccordement du c ble le montage se fait dans l ordre inverse Les sections minimales et maxima...

Page 29: ...9 Notizen Notes Remarques...

Page 30: ...10 Notizen Notes Remarques...

Page 31: ...11 Notizen Notes Remarques...

Page 32: ...er Crouse Hinds CEAG estas instrucciones de servicio en otro idioma de la Union Europea EST Seda kasutusjuhendit oma riigikeeles v ite k sida oma riigis asuvast asjaomasest Cooper Crouse Hindsi CEAG e...

Reviews: