INS #
Brand Logo
reversed out of
black
INS #
ADF142501
Start Up Behavior
Item No.
Action
1
Turn power ON to the fixture.
2
The light will start at 50% light level and then raise or
lower to the daylight level.
3
The sensor RED LED should slow blink (ON for 2
seconds, OFF for 2 seconds) for a 1 minute duration
then blink only on occupancy.
4
Wait for next daylight adjustment/occupancy action.
Factory Defaults
Occupancy Detection
Auto-on, Active
Default Occupancy Time Out
20 minutes
Occupancy Sensitivity
High
Energy Saver Scene
100% - Daytime Occupied
Scene
Fade Up Time
32% per second using “Raise”
Fade Down Time
24% per second using “Lower”
Default Daylight Harvesting Level 500 Lux
Default Unoccupied Light Level
Off
Integrated Sensor Remote Programming
Programmation à distance du détecteur intégré
Programación remota del sensor integrado
Relay On/Off
Dimmer Raise/Lower
Sensitivity Values
Push sets sensitivity to Low or High
Sensor Time Out Values
Push sets time out value to
5, 10, 15 or 20 minutes
ES – Energy Saver Scene
After 10 minutes of no
occupancy dim to this level
SET
Saves current light levels to scenes
ES, DO, DU, TO, TU NO, NU
Day Time Occupied
Day Time Unoccupied
Light levels set by using raise
lower buttons, press SET and
DO or DU
Night Time Occupied
Night Time Unoccupied
Light levels set by using raise
lower buttons, press SET and
NO or NU
Twilight Occupied
Twilight Unoccupied
Light levels set by using raise
lower buttons, press SET and
TO or TU
Remote
Raise/
Lower
Scenes:
To save scenes press SET
and select sceneLower
Programming Remote
HHPRG-MS
5
10
15
20
NO
TO
LO
SET
ES
HI
DO
NU
TU
DU
Time
Out