3.4.3 Modification of a removable version of
the assembly
The work should be carried out in compliance with NEN
3140 and NEN-EN50110 standards.
3.4.3.1
Exchanging a plug-in unit (removable
outgoing units)
Removing a plug-in unit for distribution
•
Switch off the unit concerned.
•
Open the door of the groups concerned in the cable
compartment.
•
Check that the outgoing main power circuit is isolated.
•
Remove the outgoing cable connections and the
shielding plate in the cable compartment.
•
Loosen the plug-in unit's captive fixing bolts.
•
Remove the plug-in unit.
R
EMARK
With removed plug-in unit the distribution busbars
are IP20 screened by an insulation plate.
Figure 3-36: plug-in unit with MCCB
Figure 3-37: QSA switch plug-in unit
Installing a plug-in unit for distribution
•
Ensure that the switch (switch-disconnector, MCCB) of
the plug-in unit to be installed is in the OFF position.
•
Place the plug-in unit in the compartment and secure it
with the fixing bolts.
•
Check that the outgoing main power circuit is isolated.
•
Connect the outgoing main power cables and mount
the shielding plate in the cable compartment.
•
Close the door of the compartment concerned and the
cable compartment door.
Summary of Contents for Holec Capitole 40
Page 2: ...Administrative data Issue number G01 002 Date of issue 30 09 2008...
Page 62: ...Capitole 40 62 1991 901 G01 002 Place the draw out units into position Figure 3 35...
Page 74: ...Capitole 40 74 1991 901 G01 002 Figure 4 1...
Page 76: ...Capitole 40 76 1991 901 G01 002 Figure 4 2...
Page 78: ...Capitole 40 78 1991 901 G01 002 Figure 4 3...
Page 82: ...Capitole 40 82 1991 901 G01 002 Figure 4 5 Figure 4 6...
Page 84: ...Capitole 40 84 1991 901 G01 002 Figure 4 7...
Page 86: ...Capitole 40 86 1991 901 G01 002 Figure 4 8...
Page 88: ...Capitole 40 88 1991 901 G01 002 Figure 4 9...
Page 90: ...Capitole 40 90 1991 901 G01 002 Figure 4 10...
Page 92: ...Capitole 40 92 1991 901 G01 002 Figure 4 11...
Page 94: ...Capitole 40 94 1991 901 G01 002 Figure 4 12...
Page 96: ...Capitole 40 96 1991 901 G01 002 Figure 4 13...
Page 97: ...Capitole 40 1991 901 G01 002 97 APPENDIX 1 EU DECLARATION OF CONFORMITY...
Page 98: ...Capitole 40 98 1991 901 G01 002 APPENDIX 2 KEMA TEST REPORT...
Page 99: ...Capitole 40 1991 901 G01 002 99...
Page 100: ...Capitole 40 100 1991 901 G01 002 APPENDIX 3 LLOYD S CERTIFICATE...
Page 101: ...Capitole 40 1991 901 G01 002 101...