Page 12
SK-90610-Y4_EN
4. Power cables connection
4.2 MBP11K208
1. Remove the top cover
(5)
of the MBP I/O "UPS connection" cover
(2)
after removing the 3 screws.
2. Punch the knockouts of the MBP I/O UPS connection cover
(2)
and insert 2 provided conduit fittings
inside.
1
1
3. Insert the provided conduit with blue color coding
(3)
, through the "TO UPS NORMAL AC SOURCE"
conduit fitting
take care to leave the conduit end with blue label on opposite side (for connection to UPS).
4. Connect the 3 wires of this blue color conduit
(3)
to the "TO UPS NORMAL AC SOURCE" MBP terminal
blocks.
5. Insert the provided conduit with red color coding
(4)
, through the "FROM UPS OUTPUT" conduit fitting
take care to leave the conduit end with red label on opposite side (for connection to UPS).
6. Connect the 3 wires of this red color conduit
(4)
to the "FROM UPS OUTPUT" MBP terminal blocks.
7. Put back the MBP I/O "UPS connection" cover
(2)
and secure it with 4 screws on the MBP casing.
8. Put back the top cover
(5)
of the MBP I/O "UPS connection" cover
(2)
and secure it with 3 screws.
9. Remove the I/O terminal blocks cover of the UPS - refer to the UPS user manual
10. Punch the Input and Output knockouts of the UPS I/O TB cover and insert 2 provided conduit fittings
inside.
11. Insert the conduits
(3)
and
(4)
through the previously mounted conduit fittings of the UPS I/O TB cover,
following color coding on the conduits and the UPS I/O TB cover (blue for UPS Input / red for UPS
Output) – also do not remove the UPS Input Bypass jumper inside the UPS I/O TB cover - refer to the UPS
User Manual
12. Connect the wires of the conduit with blue color coding
(3)
to the "NORMAL AC SOURCE" terminal
blocks of UPS, and the wires of the conduit with red color coding
(4)
to the "OUTPUT" terminal blocks of
UPS - refer to the UPS User Manual to check the UPS terminal blocks connection
13. Connect the MBP detection cable
(6)
to the specific UPS connector (MBP detect, refer to the UPS User
Manual).
Only with compatible EATON UPS, contact your Eaton reseller for more information.
14. Put back and secure the I/O terminal blocks cover of the UPS - refer to the UPS user manual.
15. Remove the top cover
(5)
of the MBP I/O cover
(1)
after removing the 3 screws.
2
6
4
3
5
to UPS output
to UPS
Normal
AC Source