i-on30EX 

Before You Begin 

Page 13 

 

Figure 17 Bus Wiring Configurations 

For star configurations the cable length from 
control unit to the most distant bus device should 
be kept short, and should not exceed 100m. 
There should be no more than four arms in the 
star. 

For a daisy chain configuration the total cable 
length should not exceed 1,000m.  

Bus Termination 

The i-on30EX/EXD bus uses the RS485 interface. 
Because of this the ends of the line in some 
configurations may be terminated to improve 
performance in electrically noisy environments or 
where there are long cable runs. The control unit. 
expanders and keypads have a termination link on 
their PCBs (see 16 in Fig 2 for the control unit, 5 
in Fig 7 for the keypad, 12 in Fig 14 for the wired 
expander and 11 in Fig 16 for the radio expander). 
Fitting a jumper to the pins adds a termination to 
the cable. 

In a daisy chain configuration fit the termination 
jumpers in the devices at each end of the chain 
(see Fig 17 ). 

In a star configuration: 

 

If there are only two arms on the star then this 
is the same as a daisy chain configuration 
(see “Daisy Chain 1” in Figure 17). If required 

fit the termination jumper at the devices on 
the end of each arm. 

 

If there are more than two arms AND two 
cables are long while the remaining cables 
are short (less than 10m) then it is possible to 
terminate at the two devices on the ends of 
the long cables. 

 

If there are more than two arms BUT each 
cable is more than 10m then 

DO NOT

 fit the 

termination jumpers on any of the devices. 

Voltage Drop 

In order for the system to work correctly, the 
voltage at each device must NOT drop below 
10.5V even when running on the standby battery. 
Eaton’s Security Business recommends that the 
voltage at each device should stay above 12V. 

Standard 7/0.2 alarm cable has a resistance of 8 
Ohms per 100m per core. The voltage drop is 
calculated using the following formula:  V Drop = 
Current drawn x cable length x 0.08 x 2. 

Table 1 shows the voltage drop against the 
current drawn and cable length. 

The shaded area shows where the voltage drop 
would cause the bus voltage to fall from 13.8V to 
below 12.0V when using a single core. 

Summary of Contents for i-on30EX

Page 1: ...i on30EX i on30EXD Security System Installation Guide Issue 6...

Page 2: ...erting you to potential problems or hazards Each of these are marked by the words Note Caution or WARNING Note Describes conditions that may affect the proper functioning of the equipment but will not...

Page 3: ...re Closed Circuit Connections 20 Fully Supervised Loop Connections 20 Step 7 Connect Wired Outputs 22 Control Unit Wired Outputs 22 Wired External Sounders Optional 22 Wired Outputs on Expanders 22 Wi...

Page 4: ...i on30EX EXD Page iv This page is intentionally blank...

Page 5: ...grammable output and an external prox reader KEY EP A range of wireless peripherals is available for operation with the wireless expanders The range includes a door contact universal transmitter a pas...

Page 6: ...cable The Installer Menu allows you to specify all the operating parameters for an individual installation If you wish you can also connect a PC or laptop to the mini USB port on the control unit PCB...

Page 7: ...ll affect the signal from a transmitter Please read Eaton s Security Business publication Guidance Notes for Wireless Alarm System Installations obtainable from www coopersecurity co uk for more infor...

Page 8: ...poor at transmitting radio waves Guided Tour CAUTION All printed circuit boards for the i on30EX its expanders and keypads have been tested for Electromagnetic Compatibility EMC However when handling...

Page 9: ...t 1 Connectors for system bus 2 Zone output and Aux power connectors 3 Plug by output connectors 4 Tamper switch 5 ADSL filter pins i on30EXD only 6 On board communicator connections i on30EXD only 7...

Page 10: ...XD Page 6 1 Built in communicator telephone line connector i on30EXD only 2 Siren and strobe 3 Loudspeaker 4 Bus cable connector 5 Output transistorised 6 Aux power 7 Wired zone connectors Figure 3 Co...

Page 11: ...To open the keypad first gently prise off the trim on the front and remove the two screws Next carefully lever the front of the keypad containing the PCB and display away from the keypad rear housing...

Page 12: ...to gently push the bottom edge of the caps in with the end of a small screwdriver to start them Remove the two screws hidden underneath see Figure 8 Gently swing the lower side of the front out from...

Page 13: ...inals for zones 4 Sounder volume control 5 Connector for data bus and output terminal 6 Jumpers for addressing and LED function 6a Addressing not used in i onEX control units 6b LED functions and RS48...

Page 14: ...aker connectors 19 Outputs Figure 14 EXP W10 Wired Expander 1 Cable entry also behind PCB 2 Central keyhole 3 PCB 4 Relay card i rc01 connector 5 Aux power 6 Link to enable disable front rear tamper s...

Page 15: ...sable front rear tamper switch 6 Lid tamper rear tamper behind PCB 7 Bus termination jumper 8 Addressing button 9 Fixing holes 10 Engineering keypad connector 11 Bus cable connector 12 Sounder 13 Loud...

Page 16: ...ent drawn from the Aux terminals 12V must be included in the overall calculation CAUTION Ensure that the system does not demand more than the maximum current available from the control unit during an...

Page 17: ...a star configuration If there are only two arms on the star then this is the same as a daisy chain configuration see Daisy Chain 1 in Figure 17 If required fit the termination jumper at the devices o...

Page 18: ...360mA 0 58V 1 15V 1 73V 2 30V 2 88V 3 46V 4 03V 4 61V 5 18V 5 76V 380mA 0 61V 1 22V 1 82V 2 43V 3 04V 3 65V 4 26V 4 86V 5 47V 6 08V 400mA 0 64V 1 28V 1 92V 2 56V 3 20V 3 84V 4 48V 5 12V 5 76V 6 40V Re...

Page 19: ...and location for the user Out of sight of potential intruders Do NOT site the keypad s Next to electronic equipment particularly computers photocopiers or other radio equipment CAT 5 data lines or ind...

Page 20: ...s You can set the function of the backlights in either of two ways a Use the Installer Menu Detectors Devices Wired Keypads Edit Keypad Keypad n Backlight option See the Engineering Guide for more det...

Page 21: ...on key will glow for 20 seconds after the last press this may be useful when the keypad is placed in bedrooms that should be completely dark at night MENU STATUS OK LED 4 Leave local programming mode...

Page 22: ...fixing plate and then slide it a short distance parallel to the body of the prox reader 3 Slide the fixing plate away from the reader body along the cable Figure 23 Opening External Prox Reader Figure...

Page 23: ...peakers During normal operation loudspeakers on expanders repeat setting and entry tones for the partition that the expander is allocated to During an alarm the loudspeakers repeat alarm tones Each lo...

Page 24: ...ne Wiring Two Wire Closed Circuit Connections With version 4 02 and higher software you can connect two wire CCL detectors to each pair of zone terminals To specify the zone wiring type use the Instal...

Page 25: ...on a KEY KPZ01 Note that the resistance values shows are examples Figure 35 Wiring FSL Zones on KEY KPZ01 When programming select the FSL resistor values for the control unit in Installer Menu System...

Page 26: ...minal on the control unit see item 10 in Figure 3 as either CC or FSL Use Installer Menu System Options Panel Tamper Rtn By default the terminal is CC If you program the TR terminal as FSL then make s...

Page 27: ...any other FSL resistor combinations CC wiring Eaton s Security Business does NOT recommend that you use CC wiring for this application The maximum length of wire allowable is only 6m Instead Eaton s...

Page 28: ...PABX exchanges with or without secondary proceed indication Note The built in communicator is not suitable for connection as an extension to a pay phone or to 1 1 carrier systems Approval The built i...

Page 29: ...nal Installer after 14 days written notice to the authorised maintainer To connect the telephone line see Figure 45 i Using a two core telephone cable strip off 5mm and feed the cable through one of t...

Page 30: ...hen the fault is absent Tell Back Input This input is designed to allow a plug by communicator to indicate to the control unit that the user can reset the system after a system tamper The communicator...

Page 31: ...rt pause the keypad gives a confirmation tone The display briefly shows the bus address of the keypad If there are no other keypads connected to the bus it should be b1 d51 bus 1 device 51 Keypads tak...

Page 32: ...flashes a second Each of these sequences has the following meaning No Flashes Meaning One Communication with control unit over bus is OK Two No communication over the bus in the last 10 seconds Three...

Page 33: ...trying to set the system from a keypad will see the message Installer on Site All HUAs including radio HUAs fire alarm zones 24 hour zones and tampers are disabled If you have logged into the system...

Page 34: ...ctory default options without defaulting the user and installer access codes then 1 From the Installer Menu select System Options Restore Defaults Factory Defaults The display shows 2 EITHER Press to...

Page 35: ...ed description Note make sure that you allocate keypads correctly to partitions For more information see Assigning Wired Keypads to Partitions in the i on Range Engineering Guide Assemble and close th...

Page 36: ...er Access HUA keys active Quick set Quick omit User code reqd 2 Way Replies 2 Way Set Instant Duress Enable User reset Zone alarms 6 Zone tampers System tampers Confirmation UK Confirmation Mode Basic...

Page 37: ...is disabled 18 Appears only if Report Mode Fast Format AND Confirmation Mode Basic 19 Shows None on i on30EXD 20 Must be activated by a Eaton s Security Business External Support Manager 21 Appears o...

Page 38: ...r you can employ the Test Locate Bus Device option in the Installer Menu Use this option to make a selected bus device give a continuous tone from its sounder Once you have found the bus device you ca...

Page 39: ...y available for at least 10 years without power Internal Clock 10 minutes over one year depending on the accuracy of the mains supply frequency User Codes 50 plus installer code Remote controls 50 one...

Page 40: ...h sealed lead acid not supplied Low battery fault at 12V Aux power output fault at 9V Deep discharge protection at 10 0 5V Serviceable components Mains fuse 250mA T Standby time See Power Availability...

Page 41: ...3rEUR 00 Pet tolerant PIR 714rEUR 00 PIR Transmitter Small case 720rEUR 00 Smoke Detector Transmitter 734rEUR 00 01 CC FSL Door Contact Transmitter white 734rEUR 05 06 CC FSL Door Contact Transmitter...

Page 42: ...i on30EX EXD Page 38 NOTES...

Page 43: ...i on30EX EXD Page 39 NOTES...

Page 44: ...EXD Page 40 Product Support UK Tel 44 0 1594 541978 Available between 08 30 to 17 00 Monday to Friday Product Support Fax 01594 545401 email techsupport coopersecurity co uk Part Number 12435139 21 1...

Reviews: