Installation
i-on30EXL/EXDL
Page 22
Figure 36 shows the wiring for four-wire CCL
zones on the EXP-W10 wired expander. Note that
the connections are different on the expander
compared to the control unit. Also note that zones
0, 6,7,8 and 9 are not available on the control unit,
and zones 5-9 are not available on the expander.
Wired Expander
Z0
Z1
Z2
Z3
Z4
Z5
Z6
Z7
Z8
Z9
Alarm Zone 1
Alarm Zone 2
Alarm Zone 0
Tamper Zone 1
Tamper Zone 2
Tamper Zone 0
Figure 36 Wired Expander CCL Zone Wiring
Figure 37 shows the wiring for CCL zones on the
EXP-WCC wired expander. Note that the EXP-
WCC provides connectors for a total of ten
separate 4-wire CCL detectors, and that there are
separate terminals for both alarm and tamper.
Tamper Zone 1
Alarm Zone 1
Tamper Zone 0
Alarm Zone 0
Figure 37 EXP-WCC CCL Zone Wiring
Figure 38 Wired Expander CCL Zone Wiring
Tamper Zone 1
Alarm Zone 1
KEY-KPZ01
Figure 39 KEY-KPZ01 CCL Zone Wiring
Two-Wire Closed Circuit Connections
With version 4.02 software you can connect two-
wire CCL detectors to each pair of zone terminals.
To specify the zone wiring type use the
Installer
Menu – System Options – Wire Zone Type
option and
select “2-wire CC”.
On the control unit, EXP-W10 and EXP-WCC, if
required you can use one pair of zone terminals
as a common tamper, provided you program that
zone with the type “Tamper” from the Installer
Menu.
The EXP-WCC does not specifically have a 2-wire
CC zone type. However you can mimic the setting
by usi
ng “4k7/2k2/4-wire CC” zone wiring option,
and then connecting the detector to the alarm
terminals and placing a short across the tamper
terminals.
Fully Supervised Loop Connections
Figure 40 shows the wiring connections for FSL
zones on the control unit. Note that the resistance
values shown are examples.
Figure 40 FSL Zone Wiring
– Control Unit
Figure 41 shows the wiring connections for FSL
zones on the EXP-W10 expander. Note that the
connections are different on the expander
compared with the control unit.